NA2XSY 6/10 kV; 12/20 kV; 18/30 kV

Single-conductor power cables with aluminium working conductor with radial field, with thickness cross-linked polyethylene insulation with coaxial copper return conductor and softened PVC sheath.
|
DESIGN |
|
|
Standard |
DIN VDE 0276-620: 2024-12; HD 620 S3:2023 part 0, 1 and 10C |
|
Conductor |
Aluminium multi-stranded, round of class 2 |
|
Shield on the conductor |
Semi-conductive polyethylene |
|
Insulation |
Cross-linked polyethylene |
|
Shield on the insulation |
Semi-conductive polyethylene |
|
Shield wrapping |
Semi-conductive tape |
|
Return wire |
Copper wires, round + spiral copper tape |
|
Return wire wrapping |
Polyester tape |
|
Sheath |
Softened PVC |
|
Test voltage |
3.5U0 / 5 minutes |
|
Intensity of incomplete discharge |
max. 2pC/2U0 |
|
Max. conductor temperature for long-term load |
+90°C |
|
Max. conductor temp. at 5 sec. short circuit |
+250°C |
|
Lowest permissible cable laying temperature |
-5°C |
|
Max. conductor pulling force |
30 x S (S = Al conductor cross-section in mm2) [N] |
|
Minimum bending radius |
15xD, D – cable outside diameter [mm] |
|
Intended use |
Cables intended for the transmission of electricity, for use in MV power networks with a rated voltage not exceeding U0/U = 6/10kV; 12/20 kV; 18/30 kV. For laying directly in the ground, cable ducts, conduits and in the air. |
|
Packaging |
Cable reels |
|
Reaction to fire class in accordance with EN 13501-6 |
Eca |
|
NA2XSY 6/10kV |
|||||||
|
Conductor cross-section |
Return wire cross-section |
Rated thickness of |
Approximate cable outer diameter |
Approximate cable weight |
Max. conductor resistance at temp. |
||
|
insulation |
sheath |
20°C |
90°C |
||||
|
mm2 |
mm2 |
mm |
mm |
kg/km |
Ω/km |
Ω/km |
|
|
50 |
16 |
3,4 |
2,5 |
25,8 |
770 |
0,641 |
0,825 |
|
70 |
16 |
3,4 |
2,5 |
27,5 |
863 |
0,443 |
0,570 |
|
95 |
16 |
3,4 |
2,5 |
28,7 |
974 |
0,320 |
0,412 |
|
120 |
16 |
3,4 |
2,5 |
30,1 |
1078 |
0,253 |
0,326 |
|
150 |
25 |
3,4 |
2,5 |
31,8 |
1291 |
0,206 |
0,265 |
|
185 |
25 |
3,4 |
2,5 |
33,3 |
1428 |
0,164 |
0,211 |
|
240 |
25 |
3,4 |
2,5 |
35,7 |
1640 |
0,125 |
0,161 |
|
300 |
25 |
3,4 |
2,5 |
37,7 |
1852 |
0,100 |
0,129 |
|
400 |
35 |
3,4 |
2,5 |
40,8 |
2240 |
0,0778 |
0,100 |
|
500 |
35 |
3,4 |
2,5 |
43,8 |
2604 |
0,0605 |
0,078 |
|
630 |
35 |
3,4 |
2,6 |
47,2 |
2959 |
0,0469 |
0,060 |
|
800 |
35 |
3,4 |
2,7 |
51,9 |
3728 |
0,0367 |
0,047 |
|
*By agreement between the parties, the cables can be manufactured with a return wire of a different cross-section than that shown in the table. |
|||||||
|
NA2XSY 12/20kV |
|||||||
|
Conductor cross-section |
Return wire cross-section |
Rated thickness of |
Approximate cable outer diameter |
Approximate cable weight |
Max. conductor resistance at temp. |
||
|
insulation |
sheath |
20°C |
90°C |
||||
|
mm2 |
mm2 |
mm |
mm |
kg/km |
Ω/km |
Ω/km |
|
|
50 |
16 |
5,5 |
2,5 |
29,8 |
950 |
0,641 |
0,825 |
|
70 |
16 |
5,5 |
2,5 |
31,4 |
1055 |
0,443 |
0,570 |
|
95 |
16 |
5,5 |
2,5 |
33,0 |
1176 |
0,320 |
0,412 |
|
120 |
16 |
5,5 |
2,5 |
32,9 |
1235 |
0,253 |
0,326 |
|
150 |
25 |
5,5 |
2,5 |
36,0 |
1508 |
0,206 |
0,265 |
|
185 |
25 |
5,5 |
2,5 |
37,4 |
1648 |
0,164 |
0,211 |
|
240 |
25 |
5,5 |
2,5 |
39,8 |
1875 |
0,125 |
0,161 |
|
300 |
25 |
5,5 |
2,5 |
41,8 |
2100 |
0,100 |
0,129 |
|
400 |
35 |
5,5 |
2,5 |
44,9 |
2550 |
0,0778 |
0,100 |
|
500 |
35 |
5,5 |
2,6 |
48,9 |
2951 |
0,0605 |
0,078 |
|
630 |
35 |
5,5 |
2,7 |
52,2 |
3414 |
0,0469 |
0,060 |
|
800 |
35 |
5,5 |
2,9 |
55,5 |
3983 |
0,0367 |
0,047 |
|
*By agreement between the parties, the cables can be manufactured with a return wire of a different cross-section than that shown in the table. |
|||||||
|
NA2XSY 18/30kV |
|||||||
|
Conductor cross-section |
Return wire cross-section |
Rated thickness of |
Approximate cable outer diameter |
Approximate cable weight |
Max. conductor resistance at temp. |
||
|
insulation |
sheath |
20°C |
90°C |
||||
|
mm2 |
mm2 |
mm |
mm |
kg/km |
Ω/km |
Ω/km |
|
|
50 |
16 |
8,0 |
2,5 |
34,9 |
1174 |
0,641 |
0,825 |
|
70 |
16 |
8,0 |
2,5 |
36,4 |
1286 |
0,443 |
0,570 |
|
95 |
16 |
8,0 |
2,5 |
38,0 |
1416 |
0,320 |
0,412 |
|
120 |
16 |
8,0 |
2,5 |
39,3 |
1533 |
0,253 |
0,326 |
|
150 |
25 |
8,0 |
2,5 |
41,2 |
1775 |
0,206 |
0,265 |
|
185 |
25 |
8,0 |
2,5 |
42,5 |
1922 |
0,164 |
0,211 |
|
240 |
25 |
8,0 |
2,5 |
44,9 |
2164 |
0,125 |
0,161 |
|
300 |
25 |
8,0 |
2,5 |
46,9 |
2401 |
0,100 |
0,129 |
|
400 |
35 |
8,0 |
2,6 |
50,0 |
2869 |
0,0778 |
0,100 |
|
500 |
35 |
8,0 |
2,7 |
53,0 |
3255 |
0,0605 |
0,078 |
|
630 |
35 |
8,0 |
2,9 |
57,5 |
3712 |
0,0469 |
0,060 |
|
800 |
35 |
8,0 |
3,0 |
61,5 |
4510 |
0,0367 |
0,047 |
|
*By agreement between the parties, the cables can be manufactured with a return wire of a different cross-section than that shown in the table. |
|||||||
Warianty / Variants (1)
| ID | Wariant | Symbol | |
|---|---|---|---|
| 31075 | NA2XSY 6/10kV 1x50 | NA2XSY 6/10kV; 12/20kV; 18/30kV |
Wydruk obejmuje opis rodziny i widoczną stronę wariantów. Pełny zestaw można przeglądać kolejnymi stronami.