NHXMH-J (O) 300/500 V

NHXMH-J (O) 300/500 V

Installation conductor with copper wires, with cross-linked polyethylene insulation and halogen-free material sheath, limited smoke and corrosive gas generation during combustion, with or without a protective core.

CONSTRUCTION:

Conductors

copper single-wire class 1 or multi-wire class 2, to PN-EN 60228

Insulation

cross-linked polyethylene

Insulation colour

NHXMH-O

1-conductor: black (other colours on request)

2-conductor: blue, brown

3-conductor: brown, black, grey or blue, brown, black

4-conductor: blue, brown, black, grey

5-conductor: blue, brown, black, grey, black

over 5 conductors - numbered conductors

NHXMH-J

3-conductor: green-yellow, blue, brown

4-conductor: yellow-green, black, brown, grey or yellow-green, blue, brown, black

5-conductor: green-yellow, blue, brown, black, grey over 5 conductors - numbered conductors, green-yellow

Filling compound

special halogen-free rubber

Sheath

special halogen-free, self-extinguishing, +flame-retardant, grey colour

Operating temperature

od -30⁰C do +70⁰C

Rated voltage

300/500 V

Bending radius

for single-conductor cables – 15 x conductor outer diameter 

for multi-conductorcables – 12 x conductor outer diameter 

Application

halogen-free power supply conductors for installations in facilities where human life and property must be protected against fire (hotels, hospitals, schools, airports, underground and train stations, industrial installations); conductors to be laid in dry and moist rooms, over and in plasterwork, in brick walls and directly in concrete; only permanent installation possible; in outdoor or underground installations cables must be laid in cable ducts or tubes

Test

resistance of a single cable to flame propagation (fire resistance): PN-EN 60332-1, IEC 60332-1,

DIN-VDE 0482-332-1

cable installation function maintenance E30: DIN-VDE 4102-12

insulation resistance to long-term fire impact (insulation durability) FE180: IEC 60331-11, IEC 60331-21, IEC 60331-31, DIN-VDE 0472-814

resistance of a cable bundle to flame propagation: PN-EN 60332-3-24, IEC 60332-3, DIN-VDE 482-266-2

emission of corrosive gases during combustion: PN-EN 50267, IEC 60754-2, DIN-VDE 0472-813

emission of smoke density during combustion: PN-EN 61034-1(-2), IEC 61034-1(-2), DIN-VDE 0482-1034-2

Packing

drums; other containers on customer's request

  

 

NHXMH-J(-O) 300/500V

Conductor number

and rated cross-section

[n x mm2]

Approximate

external cable diameter

[mm]

Approximate

cable weight

[kg/km]

1 x 1,5 RE

5,2

40

1 x 2,5 RE

5,5

52

1 x 4,0 RE

6,2

70

1 x 6,0 RE

6,7

91

1 x 10 RE

7,7

135

1 x 16 RE

8,7

202

1 x 25 RM

10,6

305

1 x 35 RM

11,8

396

2 x 1,5 RE

8,3

106

2 x 2,5 RE

9,1

136

2 x 4 RE

10,4

189

2 x 6 RE

11,4

244

2 x 10 RE

13,8

376

2 x 16 RE

16,0

558

2 x 25 RM

20,0

871

2 x 35 RM

22,7

1143

3 x 1,5 RE

8,7

121

3 x 2,5 RE

9,5

159

3 x 4 RE

10,9

225

3 x 6 RE

12,3

307

3 x 10 RE

14,5

462

3 x 16 RE

16,9

699

3 x 25 RM

21,6

1110

3 x 35 RM

24,2

1451

4 x 1,5 RE

9,3

142

4 x 2,5 RE

10,2

190

4 x 4 RE

12,2

282

4 x 6 RE

13,4

373

4 x 10 RE

16,0

580

4 x 16 RE

18,4

872

4 x 25 RM

23,8

1399

4 x 35 RM

26,6

1816

5 x 1,5 RE

9,9

166

5 x 2,5 RE

11,0

225

5 x 4 RE

13,2

336

5 x 6 RE

14,5

447

5 x 10 RE

17,4

697

5 x 16 RE

20,7

1086

5 x 25 RM

26,1

1692

5 x 35 RM

29,4

2220

7 x 1,5 RE

11,1

212

7 x 2,5 RE

12,2

290

12 x 1,5RE

14,0

326

12 x 2,5 RE

15,7

463

 

Warianty / Variants (72)

IDWariantSymbolPDF
17552NHXMH-O 1x1,5 300/500VNHXMH-J (O) 300/500 V
17553NHXMH-O 1x2,5 300/500VNHXMH-J (O) 300/500 V
17554NHXMH-O 1x4 300/500VNHXMH-J (O) 300/500 V
17555NHXMH-O 1x6 300/500VNHXMH-J (O) 300/500 V
17556NHXMH-O 1x10 300/500VNHXMH-J (O) 300/500 V
17557NHXMH-O 1x16 300/500VNHXMH-J (O) 300/500 V
17558NHXMH-O 2x1,5 300/500VNHXMH-J (O) 300/500 V
17559NHXMH-O 2x2,5 300/500VNHXMH-J (O) 300/500 V
17560NHXMH-O 2x4 300/500VNHXMH-J (O) 300/500 V
17561NHXMH-O 2x6 300/500VNHXMH-J (O) 300/500 V
17562NHXMH-O 2x10 300/500VNHXMH-J (O) 300/500 V
17563NHXMH-O 2x16 300/500VNHXMH-J (O) 300/500 V
17564NHXMH-O 2x25 300/500VNHXMH-J (O) 300/500 V
17565NHXMH-O 2x35 300/500VNHXMH-J (O) 300/500 V
17566NHXMH-O 3x1,5 300/500VNHXMH-J (O) 300/500 V
17567NHXMH-O 3x2,5 300/500VNHXMH-J (O) 300/500 V
17568NHXMH-O 3x4 300/500VNHXMH-J (O) 300/500 V
17569NHXMH-O 3x6 300/500VNHXMH-J (O) 300/500 V
17570NHXMH-O 3x10 300/500VNHXMH-J (O) 300/500 V
17571NHXMH-O 3x16 300/500VNHXMH-J (O) 300/500 V
17572NHXMH-O 3x25 300/500VNHXMH-J (O) 300/500 V
17573NHXMH-O 3x35 300/500VNHXMH-J (O) 300/500 V
17574NHXMH-O 4x1,5 300/500VNHXMH-J (O) 300/500 V
17575NHXMH-O 4x2,5 300/500VNHXMH-J (O) 300/500 V
17576NHXMH-O 4x4 300/500VNHXMH-J (O) 300/500 V
17577NHXMH-O 4x6 300/500VNHXMH-J (O) 300/500 V
17578NHXMH-O 4x10 300/500VNHXMH-J (O) 300/500 V
17579NHXMH-O 4x16 300/500VNHXMH-J (O) 300/500 V
17580NHXMH-O 4x25 300/500VNHXMH-J (O) 300/500 V
17581NHXMH-O 4x35 300/500VNHXMH-J (O) 300/500 V
17582NHXMH-O 5x1,5 300/500VNHXMH-J (O) 300/500 V
17583NHXMH-O 5x2,5 300/500VNHXMH-J (O) 300/500 V
17584NHXMH-O 5x4 300/500VNHXMH-J (O) 300/500 V
17585NHXMH-O 5x6 300/500VNHXMH-J (O) 300/500 V
17586NHXMH-O 5x10 300/500VNHXMH-J (O) 300/500 V
17587NHXMH-O 5x16 300/500VNHXMH-J (O) 300/500 V
17588NHXMH-O 5x25 300/500VNHXMH-J (O) 300/500 V
17589NHXMH-O 5x35 300/500VNHXMH-J (O) 300/500 V
17590NHXMH-O 7x1,5 300/500VNHXMH-J (O) 300/500 V
17591NHXMH-O 7x2,5 300/500VNHXMH-J (O) 300/500 V
17592NHXMH-J 1x1,5 300/500VNHXMH-J (O) 300/500 V
17593NHXMH-J 1x2,5 300/500VNHXMH-J (O) 300/500 V
17594NHXMH-J 1x4 300/500VNHXMH-J (O) 300/500 V
17595NHXMH-J 1x6 300/500VNHXMH-J (O) 300/500 V
17596NHXMH-J 1x10 300/500VNHXMH-J (O) 300/500 V
17597NHXMH-J 1x16 300/500VNHXMH-J (O) 300/500 V
17598NHXMH-J 3x1,5 300/500VNHXMH-J (O) 300/500 V
17599NHXMH-J 3x2,5 300/500VNHXMH-J (O) 300/500 V
17600NHXMH-J 3x4 300/500VNHXMH-J (O) 300/500 V
17601NHXMH-J 3x6 300/500VNHXMH-J (O) 300/500 V

Wydruk obejmuje opis rodziny i widoczną stronę wariantów. Pełny zestaw można przeglądać kolejnymi stronami.