NA2XS(FL)2Y 6/10kV; 12/20kV; 18/30kV

Single-conductor power cables with aluminium working conductor with cross-linked polyethylene insulation with coaxial copper return conductor sealed longitudinally and radially, with thermoplastic polyethylene sheath.
|
DESIGN |
|
|
Standard |
DIN VDE 0276-620: 2024-12; HD 620 S3:2023 part 0, 1 and 10C |
|
Conductor |
Aluminium multi-stranded, round of class 2 |
|
Shield on the conductor |
Semi-conductive polyethylene |
|
Insulation |
Cross-linked polyethylene |
|
Shield on the insulation |
Semi-conductive polyethylene |
|
Shield wrapping |
Semi-conductive water blocking tape |
|
Return wire |
Copper wires, round + spiral copper tape |
|
Return wire wrapping |
Semi-conductive water blocking tape |
|
Radial seal |
Al strip with PE copolymer longitudinally aligned |
|
Sheath |
Polyethylene |
|
Test voltage |
3,5U0/ 5 minutes |
|
Intensity of incomplete discharge |
max. 2pC/2U0 |
|
Max. conductor temperature for long-term load |
+90°C |
|
Max. conductor temp. at 5 sec. short circuit |
+250°C |
|
Lowest permissible cable laying temperature |
-20°C |
|
Max. conductor pulling force |
30 x S (S = Al conductor cross-section in mm2) [N] |
|
Minimum bending radius |
15xD, D – cable outside diameter [mm] |
|
Intended use |
Cables intended for the transmission of electricity, for use in MV power networks with a rated voltage not exceeding U0/U = 6/10kV; 8.7/15 kV; 12/20 kV; 18/30 kV. For laying directly in the ground, cable ducts, conduits and in the air. |
|
Packaging |
Cable reels |
|
Reaction to fire class in accordance with EN 13501-6 |
Eca |
|
NA2XS(FL)2Y 6/10kV |
|||||||
|
Conductor cross-section |
Return wire cross-section |
Rated thickness of |
Approximate cable outer diameter |
Approximate cable weight |
Max. conductor resistance at temp. |
||
|
insulation |
sheath |
20°C |
90°C |
||||
|
mm2 |
mm2 |
mm |
mm |
kg/km |
Ω/km |
Ω/km |
|
|
50 |
16 |
3,4 |
2,5 |
26,5 |
716 |
0,641 |
0,825 |
|
70 |
16 |
3,4 |
2,5 |
27,9 |
803 |
0,443 |
0,570 |
|
95 |
16 |
3,4 |
2,5 |
29,7 |
913 |
0,320 |
0,412 |
|
120 |
16 |
3,4 |
2,5 |
30,8 |
1006 |
0,253 |
0,326 |
|
150 |
25 |
3,4 |
2,5 |
32,9 |
1220 |
0,206 |
0,265 |
|
185 |
25 |
3,4 |
2,5 |
34,3 |
1349 |
0,164 |
0,211 |
|
240 |
25 |
3,4 |
2,5 |
36,7 |
1552 |
0,125 |
0,161 |
|
300 |
25 |
3,4 |
2,5 |
38,7 |
1761 |
0,100 |
0,129 |
|
400 |
35 |
3,4 |
2,5 |
41,6 |
2181 |
0,0778 |
0,100 |
|
500 |
35 |
3,4 |
2,5 |
44,6 |
2521 |
0,0605 |
0,078 |
|
630 |
35 |
3,4 |
2,6 |
49,2 |
2982 |
0,0469 |
0,060 |
|
800 |
35 |
3,4 |
2,7 |
52,4 |
3529 |
0,0367 |
0,047 |
|
*By agreement between the parties, the cables can be manufactured with a return wire of a different cross-section than that shown in the table. |
|||||||
|
NA2XS(FL)2Y 12/20kV |
|||||||
|
Conductor cross-section |
Return wire cross-section |
Rated thickness of |
Approximate cable outer diameter |
Approximate cable weight |
Max. conductor resistance at temp. |
||
|
insulation |
sheath |
20°C |
90°C |
||||
|
mm2 |
mm2 |
mm |
mm |
kg/km |
Ω/km |
Ω/km |
|
|
50 |
16 |
5,5 |
2,5 |
30,9 |
889 |
0,641 |
0,825 |
|
70 |
16 |
5,5 |
2,5 |
32,3 |
984 |
0,443 |
0,570 |
|
95 |
16 |
5,5 |
2,5 |
34,1 |
1071 |
0,320 |
0,412 |
|
120 |
16 |
5,5 |
2,5 |
35,2 |
1106 |
0,253 |
0,326 |
|
150 |
25 |
5,5 |
2,5 |
37,0 |
1426 |
0,206 |
0,265 |
|
185 |
25 |
5,5 |
2,5 |
38,7 |
1569 |
0,164 |
0,211 |
|
240 |
25 |
5,5 |
2,5 |
40,8 |
1782 |
0,125 |
0,161 |
|
300 |
25 |
5,5 |
2,5 |
43,1 |
2004 |
0,100 |
0,129 |
|
400 |
35 |
5,5 |
2,5 |
46,0 |
2444 |
0,0778 |
0,100 |
|
500 |
35 |
5,5 |
2,6 |
49,2 |
2817 |
0,0605 |
0,078 |
|
630 |
35 |
5,5 |
2,7 |
54,0 |
3327 |
0,0469 |
0,060 |
|
800 |
35 |
5,5 |
2,9 |
57,2 |
3901 |
0,0367 |
0,047 |
|
*By agreement between the parties, the cables can be manufactured with a return wire of a different cross-section than that shown in the table. |
|||||||
|
NA2XS(FL)2Y 18/30kV |
|||||||
|
Conductor cross-section |
Return wire cross-section |
Rated thickness of |
Approximate cable outer diameter |
Approximate cable weight |
Max. conductor resistance at temp. |
||
|
insulation |
sheath |
20°C |
90°C |
||||
|
mm2 |
mm2 |
mm |
mm |
kg/km |
Ω/km |
Ω/km |
|
|
50 |
16 |
8,0 |
2,5 |
35,7 |
1115 |
0,641 |
0,825 |
|
70 |
16 |
8,0 |
2,5 |
37,1 |
1220 |
0,443 |
0,570 |
|
95 |
16 |
8,0 |
2,5 |
38,9 |
1355 |
0,320 |
0,412 |
|
120 |
16 |
8,0 |
2,5 |
40,0 |
1462 |
0,253 |
0,326 |
|
150 |
25 |
8,0 |
2,5 |
42,1 |
1700 |
0,206 |
0,265 |
|
185 |
25 |
8,0 |
2,5 |
43,5 |
1847 |
0,164 |
0,211 |
|
240 |
25 |
8,0 |
2,5 |
45,9 |
2082 |
0,125 |
0,161 |
|
300 |
25 |
8,0 |
2,5 |
47,9 |
2317 |
0,100 |
0,129 |
|
400 |
35 |
8,0 |
2,6 |
50,8 |
2776 |
0,0778 |
0,100 |
|
500 |
35 |
8,0 |
2,7 |
54,0 |
3173 |
0,0605 |
0,078 |
|
630 |
35 |
8,0 |
2,9 |
59,0 |
3734 |
0,0469 |
0,060 |
|
800 |
35 |
8,0 |
3,0 |
62,2 |
4329 |
0,0367 |
0,047 |
|
*By agreement between the parties, the cables can be manufactured with a return wire of a different cross-section than that shown in the table. |
|||||||
Warianty / Variants (1)
| ID | Wariant | Symbol | |
|---|---|---|---|
| 31081 | NA2XS(FL)2Y 6/10kV 1x50 | NA2XS(FL)2Y 6/10kV; 12/20kV; 18/30kV |
Wydruk obejmuje opis rodziny i widoczną stronę wariantów. Pełny zestaw można przeglądać kolejnymi stronami.