N2XS(FL)2Y 6/10kV; 12/20kV; 18/30kV

Single-conductor power cables with copper working conductor with radial field, with cross-linked polyethylene insulation with coaxial copper return conductor sealed longitudinally and radially, with thermoplastic polyethylene sheath.
|
DESIGN |
|
|
Standard |
DIN VDE 0276-620: 2024-12; HD 620 S3:2023 part 0, 1 and 10C |
|
Conductor |
Multi-stranded copper, round grade 2 |
|
Shield on the conductor |
Semi-conductive polyethylene |
|
Insulation |
Cross-linked polyethylene |
|
Shield on the insulation |
Semi-conductive polyethylene |
|
Shield wrapping |
Semi-conductive water blocking tape |
|
Return wire |
Copper wires, round + spiral copper tape |
|
Return wire wrapping |
Semi-conductive water blocking tape |
|
Radial seal |
Al strip with PE copolymer longitudinally aligned |
|
Sheath |
Polyethylene |
|
Test voltage |
3,5U0/ 5 minutes |
|
Intensity of incomplete discharge |
max. 2pC/2U0 |
|
Max. conductor temperature for long-term load |
+90°C |
|
Max. conductor temp. at 5 sec. short circuit |
+250°C |
|
Lowest permissible cable laying temperature |
-20°C |
|
Max. conductor pulling force |
50 x S (S = Cu conductor cross-section in mm2) [N] |
|
Minimum bending radius |
15xD, D – cable outside diameter [mm] |
|
Intended use |
Cables intended for the transmission of electricity, for use in MV power networks with a rated voltage not exceeding U0/U = 6/10kV; 8.7/15 kV; 12/20 kV; 18/30 kV. For laying directly in the ground, cable ducts, conduits and in the air. |
|
Packaging |
Cable reels |
|
Reaction to fire class in accordance with EN 13501-6 |
Eca |
|
N2XS(FL)2Y 6/10kV |
|||||||
|
Conductor cross-section |
Return wire cross-section |
Rated thickness of |
Approximate cable outer diameter |
Approximate cable weight |
Max. conductor resistance at temp. |
||
|
insulation |
sheath |
20°C |
90°C |
||||
|
mm2 |
mm2 |
mm |
mm |
kg/km |
Ω/km |
Ω/km |
|
|
50 |
16 |
3,4 |
2,5 |
26,7 |
1029 |
0,387 |
0,495 |
|
70 |
16 |
3,4 |
2,5 |
28,1 |
1229 |
0,268 |
0,343 |
|
95 |
16 |
3,4 |
2,5 |
29,7 |
1492 |
0,193 |
0,247 |
|
120 |
16 |
3,4 |
2,5 |
31,0 |
1735 |
0,153 |
0,196 |
|
150 |
25 |
3,4 |
2,5 |
32,7 |
2123 |
0,124 |
0,159 |
|
185 |
25 |
3,4 |
2,5 |
34,2 |
2475 |
0,0991 |
0,127 |
|
240 |
25 |
3,4 |
2,5 |
37,0 |
3041 |
0,0754 |
0,097 |
|
300 |
25 |
3,4 |
2,5 |
38,6 |
3567 |
0,0601 |
0,077 |
|
400 |
35 |
3,4 |
2,5 |
41,8 |
4634 |
0,0470 |
0,060 |
|
500 |
35 |
3,4 |
2,5 |
44,8 |
5586 |
0,0366 |
0,047 |
|
630 |
35 |
3,4 |
2,6 |
49,0 |
6863 |
0,0283 |
0,036 |
|
800 |
35 |
3,4 |
2,7 |
53,0 |
8486 |
0,0221 |
0,028 |
|
*By agreement between the parties, the cables can be manufactured with a return wire of a different cross-section than that shown in the table. |
|||||||
|
N2XS(FL)2Y 12/20kV |
|||||||
|
Conductor cross-section |
Return wire cross-section |
Rated thickness of |
Approximate cable outer diameter |
Approximate cable weight |
Max. conductor resistance at temp. |
||
|
insulation |
sheath |
20°C |
90°C |
||||
|
mm2 |
mm2 |
mm |
mm |
kg/km |
Ω/km |
Ω/km |
|
|
50 |
16 |
5,5 |
2,5 |
30,9 |
1189 |
0,387 |
0,495 |
|
70 |
16 |
5,5 |
2,5 |
32,3 |
1397 |
0,268 |
0,343 |
|
95 |
16 |
5,5 |
2,5 |
33,9 |
1670 |
0,193 |
0,247 |
|
120 |
16 |
5,5 |
2,5 |
35,2 |
1921 |
0,153 |
0,196 |
|
150 |
25 |
5,5 |
2,5 |
36,9 |
2319 |
0,124 |
0,159 |
|
185 |
25 |
5,5 |
2,5 |
38,4 |
2680 |
0,0991 |
0,127 |
|
240 |
25 |
5,5 |
2,5 |
41,2 |
3264 |
0,0754 |
0,097 |
|
300 |
25 |
5,5 |
2,5 |
42,8 |
3800 |
0,0601 |
0,077 |
|
400 |
35 |
5,5 |
2,5 |
46,0 |
4884 |
0,0470 |
0,060 |
|
500 |
35 |
5,5 |
2,6 |
49,0 |
5854 |
0,0366 |
0,047 |
|
630 |
35 |
5,5 |
2,7 |
53,7 |
7159 |
0,0283 |
0,036 |
|
800 |
35 |
5,5 |
2,9 |
57,2 |
8803 |
0,0221 |
0,028 |
|
*By agreement between the parties, the cables can be manufactured with a return wire of a different cross-section than that shown in the table. |
|||||||
|
N2XS(FL)2Y 18/30kV |
|||||||
|
Conductor cross-section |
Return wire cross-section |
Rated thickness of |
Approximate cable outer diameter |
Approximate cable weight |
Max. conductor resistance at temp. |
||
|
insulation |
sheath |
20°C |
90°C |
||||
|
mm2 |
mm2 |
mm |
mm |
kg/km |
Ω/km |
Ω/km |
|
|
50 |
16 |
8,0 |
2,5 |
35,9 |
1412 |
0,387 |
0,495 |
|
70 |
16 |
8,0 |
2,5 |
37,3 |
1631 |
0,268 |
0,343 |
|
95 |
16 |
8,0 |
2,5 |
38,9 |
1915 |
0,193 |
0,247 |
|
120 |
16 |
8,0 |
2,5 |
40,2 |
2176 |
0,153 |
0,196 |
|
150 |
25 |
8,0 |
2,5 |
41,9 |
2587 |
0,124 |
0,159 |
|
185 |
25 |
8,0 |
2,5 |
43,4 |
2959 |
0,0991 |
0,127 |
|
240 |
25 |
8,0 |
2,5 |
46,2 |
3563 |
0,0754 |
0,097 |
|
300 |
25 |
8,0 |
2,5 |
47,8 |
4110 |
0,0601 |
0,077 |
|
400 |
35 |
8,0 |
2,6 |
51,0 |
5214 |
0,0470 |
0,060 |
|
500 |
35 |
8,0 |
2,7 |
54,0 |
6206 |
0,0366 |
0,047 |
|
630 |
35 |
8,0 |
2,9 |
58,7 |
7546 |
0,0283 |
0,036 |
|
800 |
35 |
8,0 |
3,0 |
62,2 |
9216 |
0,0221 |
0,028 |
|
*By agreement between the parties, the cables can be manufactured with a return wire of a different cross-section than that shown in the table. |
|||||||
Warianty / Variants (1)
| ID | Wariant | Symbol | |
|---|---|---|---|
| 31080 | N2XS(FL)2Y 6/10kV 1x50 | N2XS(FL)2Y 6/10kV; 12/20kV; 18/30kV |
Wydruk obejmuje opis rodziny i widoczną stronę wariantów. Pełny zestaw można przeglądać kolejnymi stronami.