(N)A2XH-J(-O) 0,6/1 kV B2ca

Power cable with aluminum cores (A), halogen-free polyethylene insulation (2X) and halogen-free sheath (H), with a protective conductor (J) or without a protective conductor (O).
|
CONSTRUCTION |
||
|
Conductors |
aluminium, according to PN-EN 60228 RM – round stranded class 2 |
|
|
Insulation |
special halogen-free cross-linked polyethylene XLS |
|
|
Sheath |
special halogen-free, self-extinguishing and flame retardant, black |
|
|
Insulation colours |
1-(J): green and yellow 1-(-O) core – black |
|
|
Operating temperature |
-40°C to +90°C |
|
|
Lowest installation temperature |
-5°C |
|
|
Maximum short-circuit conductor temperature |
+250°C |
|
|
Nominal voltage |
0,6/1 kV |
|
|
Minimum bending radius |
15 x D, (D – overall diameter) |
|
|
Application |
Halogen-free cables designed for installation in facilities where human life or material goods must be protected in the event of a fire, intended for use as power and control cables in buildings and public facilities with increased fire protection requirements due to the concentration of people, fixed and cultural assets i.e. hospitals, shopping centers, cinemas, theaters, museums,medium-high and high buildings). Intended for permanent laying in installation shafts, ducts, tunnels and cable rooms |
|
|
Fire performance: · Flame retardant: · Smoke density: · Gases evolved during combustion: · Reaction to fire class (according to EN 50575): single-core cables |
IEC 60332-1-2, PN-EN 60332-1-2 IEC 61034-2, PN-EN 61034-2 light transmittance values ≥ 60% < 80% IEC 60754-2, PN-EN 60754-2: pH ≥ > 4,3; conducticity <2,5μs/mm
B2ca- s1a,d0,a1 |
|
|
Packing |
Drums |
|
|
(N)A2XH-J(-O) 0,6/1 kV B2ca |
||
|
Number and nominal cross-section of conductor [n x mm2] |
Approximate external cable diameter [mm] |
Approximate cable weight [kg/km] |
|
1 x 25 RM |
10,3 |
149 |
|
1 x 35 RM |
11,3 |
184 |
|
1 x50 RM |
12,7 |
235 |
|
1 x 70 RM |
14,6 |
317 |
|
1 x 95 RM |
16,4 |
409 |
|
1 x 120 RM |
17,9 |
499 |
|
1 x 150 RM |
20,2 | 621 |
|
1 x 185 RM |
22,1 | 761 |
|
1 x 240 RM |
24,5 | 954 |
Warianty / Variants (18)
| ID | Wariant | Symbol | |
|---|---|---|---|
| 30333 | (N)A2XH-J 0,6/1kV B2ca 1x25RM | (N)A2XH-J(-O) 0,6/1 kV B2ca | |
| 30334 | (N)A2XH-J 0,6/1kV B2ca 1x35RM | (N)A2XH-J(-O) 0,6/1 kV B2ca | |
| 30335 | (N)A2XH-J 0,6/1kV B2ca 1x50RM | (N)A2XH-J(-O) 0,6/1 kV B2ca | |
| 30336 | (N)A2XH-J 0,6/1kV B2ca 1x70RM | (N)A2XH-J(-O) 0,6/1 kV B2ca | |
| 30337 | (N)A2XH-J 0,6/1kV B2ca 1x95RM | (N)A2XH-J(-O) 0,6/1 kV B2ca | |
| 30338 | (N)A2XH-J 0,6/1kV B2ca 1x120RM | (N)A2XH-J(-O) 0,6/1 kV B2ca | |
| 30339 | (N)A2XH-J 0,6/1kV B2ca 1x150RM | (N)A2XH-J(-O) 0,6/1 kV B2ca | |
| 30340 | (N)A2XH-J 0,6/1kV B2ca 1x185RM | (N)A2XH-J(-O) 0,6/1 kV B2ca | |
| 30341 | (N)A2XH-J 0,6/1kV B2ca 1x240RM | (N)A2XH-J(-O) 0,6/1 kV B2ca | |
| 30342 | (N)A2XH-O 0,6/1kV B2ca 1x25RM | (N)A2XH-J(-O) 0,6/1 kV B2ca | |
| 30343 | (N)A2XH-O 0,6/1kV B2ca 1x35RM | (N)A2XH-J(-O) 0,6/1 kV B2ca | |
| 30344 | (N)A2XH-O 0,6/1kV B2ca 1x50RM | (N)A2XH-J(-O) 0,6/1 kV B2ca | |
| 30345 | (N)A2XH-O 0,6/1kV B2ca 1x70RM | (N)A2XH-J(-O) 0,6/1 kV B2ca | |
| 30346 | (N)A2XH-O 0,6/1kV B2ca 1x95RM | (N)A2XH-J(-O) 0,6/1 kV B2ca | |
| 30347 | (N)A2XH-O 0,6/1kV B2ca 1x120RM | (N)A2XH-J(-O) 0,6/1 kV B2ca | |
| 30348 | (N)A2XH-O 0,6/1kV B2ca 1x150RM | (N)A2XH-J(-O) 0,6/1 kV B2ca | |
| 30349 | (N)A2XH-O 0,6/1kV B2ca 1x185RM | (N)A2XH-J(-O) 0,6/1 kV B2ca | |
| 30350 | (N)A2XH-O 0,6/1kV B2ca 1x240RM | (N)A2XH-J(-O) 0,6/1 kV B2ca |