L2 - BUS(zew)

Symmetrical cable with copper multi-wire conductors in polyethylene foam insulation with thin layer of solid polyethylene (02YS) and polyethylene sheath (2Y), with common shield on central core in the form of an AL/PET tape and with second braid in the form of a braid of copper wires (C).
|
CONSTRUCTION: |
|
|
Conductors |
copper, single- or multi-wire |
|
Insulation |
special polyethylene foam with thin layer of solid polyethylene |
|
Central core |
pairs stranded into a central core, wrapped in a polyester tape |
|
Insulation colours |
red, green |
|
Shield |
in the form of an AL/PET tape on the central core, braid of braid of copper zinc-coated wires |
|
Sheath |
special polyethylene, UV resistant, black |
|
Operating temperature |
-40°C to +70°C |
|
Bend radius |
min. bend radius 10 x cable diameter |
|
Application |
L2-BUS cables are intended for connecting L2-BUS components (using RS485 standard) for sending analogue and digital signals, used in interiors (internal type), for laying in soil and on constructions |
|
Technical parameters |
wave impedance: 150 Ω ±10% conductor loop resistance (max.): 115 Ω/km shield resistance (max.): 9,7 Ω/km capacitance: 30 nF/km wave attenuation at 1 MHz = 1,2 dB/100 m 4 MHz = 2,2 dB/100 m 10 MHz = 3,2 dB/100 m 16 MHz = 4,2 dB/100 m |
|
Packing |
coils, drums |
|
|
L2-BUS (02YS(St)CY) |
|
|
Ilość par x przekrój znamionowy żył [n x 2 x mm2] |
Przybliżona średnica zewnętrzna przewodu [mm] |
Orientacyjna masa przewodu [kg/km] |
|
Number of pairs x nominal cross-section of conductor [n x 2 x mm2] |
Approximate externalcable diameter [mm] |
Approximate cable weight [kg/km] |
|
1 x 2 x 0,64 |
7,7 |
60,8 |
Warianty / Variants (1)
| ID | Wariant | Symbol | |
|---|---|---|---|
| 27671 | L2 - BUS(zew) 1x2x0,64 | L2 - BUS(zew) |
Wydruk obejmuje opis rodziny i widoczną stronę wariantów. Pełny zestaw można przeglądać kolejnymi stronami.