XnHKXS1 6/10kV; 8,7/15kV; 12/20kV; 18/30kV

XnHKXS1 6/10kV; 8,7/15kV; 12/20kV; 18/30kV

Single-conductor power cables (K) with copper conductor with radial field (H), with normal thickness (1) cross-linked polyethylene (XS) insulation with coaxial copper return wire and increased flame propagation resistance polyethylene (Xn) sheath.

DESIGN

Standard

PN-HD 620 S3:2023-04 part 0, 1 and 10R

Conductor

Multi-stranded copper, round grade 2

Shield on the conductor

Semi-conductive polyethylene

Insulation

Cross-linked polyethylene

Shield on the insulation

Semi-conductive polyethylene

Shield wrapping

Semi-conductive tape

Return wire

Copper wires, round + spiral copper tape

Return wire wrapping

Polyester tape

Sheath

Thermoplastic polyethylene

Test voltage

3,5U0/ 5 minutes

Intensity of incomplete discharge

max. 2pC/2U0

Max. conductor temperature for long-term load

+90°C

Max. conductor temp. at 5 sec. short circuit

+250°C

Lowest permissible cable laying temperature

-20°C

Minimum ambient temperature for permanent cable installation

-30°C

Max. conductor pulling force

50 x S (S = Cu conductor cross-section in mm2) [N]

Minimum bending radius

15xD, D – cable outside diameter [mm]

Intended use

Cables intended for the transmission of electricity, for use in MV power networks with a rated voltage not exceeding U0/U = 6/10kV; 8.7/15 kV; 12/20 kV; 18/30 kV. For laying directly in the ground, cable ducts, conduits and in the air.

Packaging

Cable reels

Reaction to fire class in accordance with EN 13501-6

Eca

 

XnHKXS1

6/10kV

Conductor cross-section

Return wire cross-section

Rated thickness of

Approximate cable outer diameter

Approximate cable weight

Max. conductor resistance at temp.

insulation

sheath

 20°C

90°C 

mm2

mm2

mm

mm

kg/km

Ω/km

Ω/km

50

16

3,4

2,5

25,5

970

0,387

0,495

70

25

3,4

2,5

27,0

1257

0,268

0,343

95

35

3,4

2,5

28,8

1610

0,193

0,247

120

25

3,4

2,5

29,9

1758

0,153

0,196

120

50

3,4

2,5

30,3

1993

0,153

0,196

150

25

3,4

2,5

31,6

1968

0,124

0,159

150

50

3,4

2,5

32,0

2286

0,124

0,159

185

25

3,4

2,5

33,1

2405

0,0991

0,127

185

50

3,4

2,5

33,5

2635

0,0991

0,127

240

25

3,4

2,5

35,9

2970

0,0754

0,097

240

50

3,4

2,5

36,3

3206

0,0754

0,097

300

25

3,4

2,5

37,5

3494

0,0601

0,077

300

50

3,4

2,5

37,9

3725

0,0601

0,077

400

50

3,4

2,5

41,5

4722

0,0470

0,060

500

50

3,4

2,5

43,6

5649

0,0366

0,047

630

50

3,4

2,6

48,2

6891

0,0283

0,036

800

50

3,4

2,7

51,5

8500

0,0221

0,028

*By agreement between the parties, the cables can be manufactured with a return wire of a different cross-section than that shown in the table.

 

XnHKXS1

8,7/15kV

Conductor cross-section

Return wire cross-section

Rated thickness of

Approximate cable outer diameter

Approximate cable weight

Max. conductor resistance at temp.

insulation

sheath

 20°C

 90°C

mm2

mm2

mm

mm

kg/km

Ω/km

Ω/km

50

16

4,5

2,5

27,8

1054

0,387

0,495

70

25

4,5

2,5

29,2

1343

0,268

0,343

95

35

4,5

2,5

31,3

1698

0,193

0,247

120

25

4,5

2,5

32,2

1851

0,153

0,196

120

50

4,5

2,5

32,6

2075

0,153

0,196

150

25

4,5

2,5

33,9

2153

0,124

0,159

150

50

4,5

2,5

34,3

2378

0,124

0,159

185

25

4,5

2,5

35,4

2507

0,0991

0,127

185

50

4,5

2,5

35,8

2732

0,0991

0,127

240

25

4,5

2,5

38,2

3080

0,0754

0,097

240

50

4,5

2,5

38,6

3305

0,0754

0,097

300

25

4,5

2,5

40,2

3619

0,0601

0,077

300

50

4,5

2,5

40,6

3843

0,0601

0,077

400

50

4,5

2,5

42,9

4810

0,0470

0,060

500

50

4,5

2,5

45,9

5764

0,0366

0,047

630

50

4,5

2,6

50,9

7051

0,0283

0,036

800

50

4,5

2,8

54,2

8670

0,0221

0,028

*By agreement between the parties, the cables can be manufactured with a return wire of a different cross-section than that shown in the table.

 

XnHKXS1

12/20kV

Conductor cross-section

Return wire cross-section

Rated thickness of

Approximate cable outer diameter

Approximate cable weight

Max. conductor resistance at temp.

insulation

sheath

 20°C

90°C 

mm2

mm2

mm

mm

kg/km

Ω/km

Ω/km

50

16

5,5

2,5

29,5

1133

0,387

0,495

70

25

5,5

2,5

31,1

1434

0,268

0,343

95

35

5,5

2,5

33,0

1793

0,193

0,247

120

25

5,5

2,5

34,0

1949

0,153

0,196

120

50

5,5

2,5

34,5

2184

0,153

0,196

150

25

5,5

2,5

35,7

2257

0,124

0,159

150

50

5,5

2,5

36,1

2487

0,124

0,159

185

25

5,5

2,5

37,2

2616

0,0991

0,127

185

50

5,5

2,5

37,6

2850

0,0991

0,127

240

25

5,5

2,5

40,0

3200

0,0754

0,097

240

50

5,5

2,5

40,5

3435

0,0754

0,097

300

25

5,5

2,5

42,0

3745

0,0601

0,077

300

50

5,5

2,5

42,4

3975

0,0601

0,077

400

50

5,5

2,5

44,8

4957

0,0470

0,060

500

50

5,5

2,6

47,7

5917

0,0366

0,047

630

50

5,5

2,7

52,8

7238

0,0283

0,036

800

50

5,5

2,8

56,2

8884

0,0221

0,028

*By agreement between the parties, the cables can be manufactured with a return wire of a different cross-section than that shown in the table.

 

XnHKXS1

18/30kV

Conductor cross-section

Return wire cross-section

Rated thickness of

Approximate cable outer diameter

Approximate cable weight

Max. conductor resistance at temp.

insulation

sheath

 20°C

90°C 

mm2

mm2

mm

mm

kg/km

Ω/km

Ω/km

50

16

8,0

2,5

34,8

1364

0,387

0,495

70

25

8,0

2,5

36,2

1671

0,268

0,343

95

35

8,0

2,5

38,4

2044

0,193

0,247

120

25

8,0

2,5

39,2

2210

0,153

0,196

120

50

8,0

2,5

39,6

2437

0,153

0,196

150

25

8,0

2,5

40,9

2530

0,124

0,159

150

50

8,0

2,5

41,4

2760

0,124

0,159

185

25

8,0

2,5

42,4

2900

0,0991

0,127

185

50

8,0

2,5

42,8

3130

0,0991

0,127

240

25

8,0

2,5

45,2

3500

0,0754

0,097

240

50

8,0

2,5

45,7

3734

0,0754

0,097

300

25

8,0

2,5

46,8

4049

0,0601

0,077

300

50

8,0

2,5

47,3

4280

0,0601

0,077

400

50

8,0

2,6

50,2

5305

0,0470

0,060

500

50

8,0

2,7

53,4

6310

0,0366

0,047

630

50

8,0

2,9

57,8

7625

0,0283

0,036

800

50

8,0

3,0

61,6

9312

0,0221

0,028

*By agreement between the parties, the cables can be manufactured with a return wire of a different cross-section than that shown in the table.

 

Warianty / Variants (51)

IDWariantSymbolPDF
30363XnHKXS 6/10kV 1x35/16XnHKXS1 6/10kV; 8,7/15kV; 12/20kV; 18/30kV
30917XnHKXS 6/10kV 1x50/16XnHKXS1 6/10kV; 8,7/15kV; 12/20kV; 18/30kV
30918XnHKXS 6/10kV 1x70/25XnHKXS1 6/10kV; 8,7/15kV; 12/20kV; 18/30kV
30919XnHKXS 6/10kV 1x95/35XnHKXS1 6/10kV; 8,7/15kV; 12/20kV; 18/30kV
30920XnHKXS 6/10kV 1x120/50XnHKXS1 6/10kV; 8,7/15kV; 12/20kV; 18/30kV
30921XnHKXS 6/10kV 1x150/50XnHKXS1 6/10kV; 8,7/15kV; 12/20kV; 18/30kV
30922XnHKXS 6/10kV 1x185/50XnHKXS1 6/10kV; 8,7/15kV; 12/20kV; 18/30kV
30923XnHKXS 6/10kV 1x240/50XnHKXS1 6/10kV; 8,7/15kV; 12/20kV; 18/30kV
30924XnHKXS 6/10kV 1x300/50XnHKXS1 6/10kV; 8,7/15kV; 12/20kV; 18/30kV
30925XnHKXS 6/10kV 1x400/50XnHKXS1 6/10kV; 8,7/15kV; 12/20kV; 18/30kV
30926XnHKXS 6/10kV 1x500/50XnHKXS1 6/10kV; 8,7/15kV; 12/20kV; 18/30kV
30927XnHKXS 6/10kV 1x630/50XnHKXS1 6/10kV; 8,7/15kV; 12/20kV; 18/30kV
30928XnHKXS 6/10kV 1x800/50XnHKXS1 6/10kV; 8,7/15kV; 12/20kV; 18/30kV
30929XnHKXS 8,7/15kV 1x35/16XnHKXS1 6/10kV; 8,7/15kV; 12/20kV; 18/30kV
30930XnHKXS 8,7/15kV 1x50/16XnHKXS1 6/10kV; 8,7/15kV; 12/20kV; 18/30kV
30931XnHKXS 8,7/15kV 1x70/25XnHKXS1 6/10kV; 8,7/15kV; 12/20kV; 18/30kV
30932XnHKXS 8,7/15kV 1x95/35XnHKXS1 6/10kV; 8,7/15kV; 12/20kV; 18/30kV
30933XnHKXS 8,7/15kV 1x120/50XnHKXS1 6/10kV; 8,7/15kV; 12/20kV; 18/30kV
30934XnHKXS 8,7/15kV 1x150/50XnHKXS1 6/10kV; 8,7/15kV; 12/20kV; 18/30kV
30935XnHKXS 8,7/15kV 1x185/50XnHKXS1 6/10kV; 8,7/15kV; 12/20kV; 18/30kV
30936XnHKXS 8,7/15kV 1x240/50XnHKXS1 6/10kV; 8,7/15kV; 12/20kV; 18/30kV
30937XnHKXS 8,7/15kV 1x300/50XnHKXS1 6/10kV; 8,7/15kV; 12/20kV; 18/30kV
30938XnHKXS 8,7/15kV 1x400/50XnHKXS1 6/10kV; 8,7/15kV; 12/20kV; 18/30kV
30939XnHKXS 8,7/15kV 1x500/50XnHKXS1 6/10kV; 8,7/15kV; 12/20kV; 18/30kV
30940XnHKXS 8,7/15kV 1x630/50XnHKXS1 6/10kV; 8,7/15kV; 12/20kV; 18/30kV
30941XnHKXS 8,7/15kV 1x800/50XnHKXS1 6/10kV; 8,7/15kV; 12/20kV; 18/30kV
30942XnHKXS 12/20kV 1x35/16XnHKXS1 6/10kV; 8,7/15kV; 12/20kV; 18/30kV
30943XnHKXS 12/20kV 1x50/16XnHKXS1 6/10kV; 8,7/15kV; 12/20kV; 18/30kV
30944XnHKXS 12/20kV 1x70/25XnHKXS1 6/10kV; 8,7/15kV; 12/20kV; 18/30kV
30945XnHKXS 12/20kV 1x95/35XnHKXS1 6/10kV; 8,7/15kV; 12/20kV; 18/30kV
30946XnHKXS 12/20kV 1x120/50XnHKXS1 6/10kV; 8,7/15kV; 12/20kV; 18/30kV
30947XnHKXS 12/20kV 1x150/50XnHKXS1 6/10kV; 8,7/15kV; 12/20kV; 18/30kV
30948XnHKXS 12/20kV 1x185/50XnHKXS1 6/10kV; 8,7/15kV; 12/20kV; 18/30kV
30949XnHKXS 12/20kV 1x240/50XnHKXS1 6/10kV; 8,7/15kV; 12/20kV; 18/30kV
30950XnHKXS 12/20kV 1x300/50XnHKXS1 6/10kV; 8,7/15kV; 12/20kV; 18/30kV
30951XnHKXS 12/20kV 1x400/50XnHKXS1 6/10kV; 8,7/15kV; 12/20kV; 18/30kV
30952XnHKXS 12/20kV 1x500/50XnHKXS1 6/10kV; 8,7/15kV; 12/20kV; 18/30kV
30953XnHKXS 12/20kV 1x630/50XnHKXS1 6/10kV; 8,7/15kV; 12/20kV; 18/30kV
30954XnHKXS 12/20kV 1x800/50XnHKXS1 6/10kV; 8,7/15kV; 12/20kV; 18/30kV
30955XnHKXS 18/30kV 1x50/16XnHKXS1 6/10kV; 8,7/15kV; 12/20kV; 18/30kV
30956XnHKXS 18/30kV 1x70/25XnHKXS1 6/10kV; 8,7/15kV; 12/20kV; 18/30kV
30957XnHKXS 18/30kV 1x95/35XnHKXS1 6/10kV; 8,7/15kV; 12/20kV; 18/30kV
30958XnHKXS 18/30kV 1x120/50XnHKXS1 6/10kV; 8,7/15kV; 12/20kV; 18/30kV
30959XnHKXS 18/30kV 1x150/50XnHKXS1 6/10kV; 8,7/15kV; 12/20kV; 18/30kV
30960XnHKXS 18/30kV 1x185/50XnHKXS1 6/10kV; 8,7/15kV; 12/20kV; 18/30kV
30961XnHKXS 18/30kV 1x240/50XnHKXS1 6/10kV; 8,7/15kV; 12/20kV; 18/30kV
30962XnHKXS 18/30kV 1x300/50XnHKXS1 6/10kV; 8,7/15kV; 12/20kV; 18/30kV
30963XnHKXS 18/30kV 1x400/50XnHKXS1 6/10kV; 8,7/15kV; 12/20kV; 18/30kV
30964XnHKXS 18/30kV 1x500/50XnHKXS1 6/10kV; 8,7/15kV; 12/20kV; 18/30kV
30965XnHKXS 18/30kV 1x630/50XnHKXS1 6/10kV; 8,7/15kV; 12/20kV; 18/30kV

Wydruk obejmuje opis rodziny i widoczną stronę wariantów. Pełny zestaw można przeglądać kolejnymi stronami.