XRUHKXS1 6/10kV; 8,7/15kV; 12/20kV; 18/30kV

Single-conductor power cables (K) with copper conductor with radial field (H), with normal thickness (1) cross-linked polyethylene (XS) insulation with coaxial copper return wire sealed longitudinally (U) and radially (R), with thermoplastic polyethylene (X), sheath.
|
DESIGN |
|
|
Standard |
PN-HD 620 S3:2023-04 part 0, 1 and 10R |
|
Conductor |
Multi-stranded copper, round grade 2 |
|
Shield on the conductor |
Semi-conductive polyethylene |
|
Insulation |
Cross-linked polyethylene |
|
Shield on the insulation |
Semi-conductive polyethylene |
|
Shield wrapping |
Semi-conductive water blocking tape |
|
Return wire |
Copper wires, round + spiral copper tape |
|
Return wire wrapping |
Semi-conductive water blocking tape |
|
Radial seal |
Al strip with PE copolymer longitudinally aligned |
|
Sheath |
Polyethylene |
|
Test voltage |
3,5U0/ 5 minutes |
|
Intensity of incomplete discharge |
max. 2pC/2U0 |
|
Max. conductor temperature for long-term load |
+90°C |
|
Max. conductor temp. at 5 sec. short circuit |
+250°C |
|
Lowest permissible cable laying temperature |
-20°C |
|
Max. conductor pulling force |
50 x S (S = Cu conductor cross-section in mm2) [N] |
|
Minimum bending radius |
15xD, D – cable outside diameter [mm] |
|
Intended use |
Cables intended for the transmission of electricity, for use in MV power networks with a rated voltage not exceeding U0/U = 6/10kV; 8.7/15 kV; 12/20 kV; 18/30 kV. For laying directly in the ground, cable ducts, conduits and in the air. |
|
Packaging |
Cable reels |
|
Reaction to fire class in accordance with EN 13501-6 |
Eca |
|
XRUHKXS1 6/10kV |
|||||||
|
Conductor cross-section |
Return wire cross-section |
Rated thickness of |
Approximate cable outer diameter |
Approximate cable weight
|
Max. conductor resistance at temp. |
||
|
insulation |
sheath |
20°C |
90°C |
||||
|
mm2 |
mm2 |
mm |
mm |
kg/km |
Ω/km |
Ω/km |
|
|
50 |
16 |
3,4 |
2,5 |
26,3 |
1005 |
0,387 |
0,495 |
|
70 |
25 |
3,4 |
2,5 |
27,7 |
1300 |
0,268 |
0,343 |
|
95 |
35 |
3,4 |
2,5 |
29,8 |
1644 |
0,193 |
0,247 |
|
120 |
25 |
3,4 |
2,5 |
30,6 |
1794 |
0,153 |
0,196 |
|
120 |
50 |
3,4 |
2,5 |
31,0 |
2023 |
0,153 |
0,196 |
|
150 |
25 |
3,4 |
2,5 |
32,3 |
2092 |
0,124 |
0,159 |
|
150 |
50 |
3,4 |
2,5 |
32,8 |
2322 |
0,124 |
0,159 |
|
185 |
25 |
3,4 |
2,5 |
33,8 |
2365 |
0,0991 |
0,127 |
|
185 |
50 |
3,4 |
2,5 |
34,3 |
2672 |
0,0991 |
0,127 |
|
240 |
25 |
3,4 |
2,5 |
36,6 |
2934 |
0,0754 |
0,097 |
|
240 |
50 |
3,4 |
2,5 |
37,1 |
3240 |
0,0754 |
0,097 |
|
300 |
25 |
3,4 |
2,5 |
38,2 |
3534 |
0,0601 |
0,077 |
|
300 |
50 |
3,4 |
2,5 |
38,7 |
3767 |
0,0601 |
0,077 |
|
400 |
50 |
3,4 |
2,5 |
41,4 |
4736 |
0,0470 |
0,060 |
|
500 |
50 |
3,4 |
2,5 |
44,8 |
5701 |
0,0366 |
0,047 |
|
630 |
50 |
3,4 |
2,6 |
48,7 |
6916 |
0,0283 |
0,036 |
|
800 |
50 |
3,4 |
2,7 |
52,4 |
8542 |
0,0221 |
0,028 |
|
*By agreement between the parties, the cables can be manufactured with a return wire of a different cross-section than that shown in the table. |
|||||||
|
XRUHKXS1 8,7/15kV |
|||||||
|
Conductor cross-section |
Return wire cross-section |
Rated thickness of |
Approximate cable outer diameter |
Approximate cable weight
|
Max. conductor resistance at temp. |
||
|
insulation |
sheath |
20°C |
90°C |
||||
|
mm2 |
mm2 |
mm |
mm |
kg/km |
Ω/km |
Ω/km |
|
|
50 |
16 |
4,5 |
2,5 |
28,5 |
1085 |
0,387 |
0,495 |
|
70 |
25 |
4,5 |
2,5 |
29,9 |
1385 |
0,268 |
0,343 |
|
95 |
35 |
4,5 |
2,5 |
32,0 |
1732 |
0,193 |
0,247 |
|
120 |
25 |
4,5 |
2,5 |
32,8 |
1887 |
0,153 |
0,196 |
|
120 |
50 |
4,5 |
2,5 |
33,3 |
2117 |
0,153 |
0,196 |
|
150 |
25 |
4,5 |
2,5 |
34,5 |
2191 |
0,124 |
0,159 |
|
150 |
50 |
4,5 |
2,5 |
35,0 |
2420 |
0,124 |
0,159 |
|
185 |
25 |
4,5 |
2,5 |
36,0 |
2469 |
0,0991 |
0,127 |
|
185 |
50 |
4,5 |
2,5 |
36,5 |
2775 |
0,0991 |
0,127 |
|
240 |
25 |
4,5 |
2,5 |
38,8 |
3046 |
0,0754 |
0,097 |
|
240 |
50 |
4,5 |
2,5 |
39,3 |
3352 |
0,0754 |
0,097 |
|
300 |
25 |
4,5 |
2,5 |
40,4 |
3652 |
0,0601 |
0,077 |
|
300 |
50 |
4,5 |
2,5 |
40,9 |
3886 |
0,0601 |
0,077 |
|
400 |
50 |
4,5 |
2,5 |
43,6 |
4873 |
0,0470 |
0,060 |
|
500 |
50 |
4,5 |
2,5 |
47,0 |
5838 |
0,0366 |
0,047 |
|
630 |
50 |
4,5 |
2,6 |
50,9 |
7065 |
0,0283 |
0,036 |
|
800 |
50 |
4,5 |
2,8 |
54,6 |
8704 |
0,0221 |
0,028 |
|
*By agreement between the parties, the cables can be manufactured with a return wire of a different cross-section than that shown in the table. |
|||||||
|
XRUHKXS1 12/20kV |
|||||||
|
Conductor cross-section |
Return wire cross-section |
Rated thickness of |
Approximate cable outer diameter |
Approximate cable weight
|
Max. conductor resistance at temp. |
||
|
insulation |
sheath |
20°C |
90°C |
||||
|
mm2 |
mm2 |
mm |
mm |
kg/km |
Ω/km |
Ω/km |
|
|
50 |
16 |
5,5 |
2,5 |
30,7 |
1179 |
0,387 |
0,495 |
|
70 |
25 |
5,5 |
2,5 |
32,1 |
1474 |
0,268 |
0,343 |
|
95 |
35 |
5,5 |
2,5 |
34,2 |
1835 |
0,193 |
0,247 |
|
120 |
25 |
5,5 |
2,5 |
35,0 |
1998 |
0,153 |
0,196 |
|
120 |
50 |
5,5 |
2,5 |
35,5 |
2228 |
0,153 |
0,196 |
|
150 |
25 |
5,5 |
2,5 |
36,7 |
2308 |
0,124 |
0,159 |
|
150 |
50 |
5,5 |
2,5 |
37,2 |
2538 |
0,124 |
0,159 |
|
185 |
25 |
5,5 |
2,5 |
38,2 |
2669 |
0,0991 |
0,127 |
|
185 |
50 |
5,5 |
2,5 |
38,7 |
2900 |
0,0991 |
0,127 |
|
240 |
25 |
5,5 |
2,5 |
41,0 |
3252 |
0,0754 |
0,097 |
|
240 |
50 |
5,5 |
2,5 |
41,5 |
3481 |
0,0754 |
0,097 |
|
300 |
25 |
5,5 |
2,5 |
42,6 |
3718 |
0,0601 |
0,077 |
|
300 |
50 |
5,5 |
2,5 |
43,1 |
4016 |
0,0601 |
0,077 |
|
400 |
50 |
5,5 |
2,5 |
45,8 |
5008 |
0,0470 |
0,060 |
|
500 |
50 |
5,5 |
2,6 |
48,8 |
5977 |
0,0366 |
0,047 |
|
630 |
50 |
5,5 |
2,7 |
53,7 |
7300 |
0,0283 |
0,036 |
|
800 |
50 |
5,5 |
2,9 |
57,2 |
8945 |
0,0221 |
0,028 |
|
*By agreement between the parties, the cables can be manufactured with a return wire of a different cross-section than that shown in the table. |
|||||||
|
XRUHKXS1 18/30kV |
|||||||
|
Conductor cross-section |
Return wire cross-section |
Rated thickness of |
Approximate cable outer diameter |
Approximate cable weight
|
Max. conductor resistance at temp. |
||
|
insulation |
sheath |
20°C |
90°C |
||||
|
mm2 |
mm2 |
mm |
mm |
kg/km |
Ω/km |
Ω/km |
|
|
50 |
16 |
8,0 |
2,5 |
35,5 |
1305 |
0,387 |
0,495 |
|
70 |
25 |
8,0 |
2,5 |
36,9 |
1721 |
0,268 |
0,343 |
|
95 |
35 |
8,0 |
2,5 |
39,0 |
2086 |
0,193 |
0,247 |
|
120 |
25 |
8,0 |
2,5 |
39,8 |
2256 |
0,153 |
0,196 |
|
120 |
50 |
8,0 |
2,5 |
40,2 |
2488 |
0,153 |
0,196 |
|
150 |
25 |
8,0 |
2,5 |
41,5 |
2578 |
0,124 |
0,159 |
|
150 |
50 |
8,0 |
2,5 |
42,0 |
2809 |
0,124 |
0,159 |
|
185 |
25 |
8,0 |
2,5 |
43,0 |
2951 |
0,0991 |
0,127 |
|
185 |
50 |
8,0 |
2,5 |
43,5 |
3181 |
0,0991 |
0,127 |
|
240 |
25 |
8,0 |
2,5 |
45,4 |
3541 |
0,0754 |
0,097 |
|
240 |
50 |
8,0 |
2,5 |
45,9 |
3790 |
0,0754 |
0,097 |
|
300 |
25 |
8,0 |
2,5 |
47,4 |
4106 |
0,0601 |
0,077 |
|
300 |
50 |
8,0 |
2,5 |
48,1 |
4337 |
0,0601 |
0,077 |
|
400 |
50 |
8,0 |
2,7 |
50,8 |
5369 |
0,0470 |
0,060 |
|
500 |
50 |
8,0 |
2,8 |
54,2 |
6394 |
0,0366 |
0,047 |
|
630 |
50 |
8,0 |
2,9 |
58,8 |
7731 |
0,0283 |
0,036 |
|
800 |
50 |
8,0 |
3,0 |
62,6 |
9412 |
0,0221 |
0,028 |
|
*By agreement between the parties, the cables can be manufactured with a return wire of a different cross-section than that shown in the table. |
|||||||