XUHAKXS1 6/10kV; 8,7/15kV; 12/20kV; 18/30kV

XUHAKXS1 6/10kV; 8,7/15kV; 12/20kV; 18/30kV

Single-conductor power cables (K) with aluminium (A) conductor with radial field (H), with normal thickness (1) cross-linked polyethylene (XS) insulation with coaxial copper return wire sealed longitudinally (U) and thermoplastic polyethylene (X) sheath.

DESIGN

Standard

PN-HD 620 S3:2023-04 part 0, 1 and 10R

Conductor

Aluminium multi-stranded, round of class 2

Shield on the conductor

Semi-conductive polyethylene

Insulation

Cross-linked polyethylene

Shield on the insulation

Semi-conductive polyethylene

Shield wrapping

Semi-conductive water blocking tape

Return wire

Copper wires, round + spiral copper tape

Return wire wrapping

Non-conductive water blocking tape

Sheath

Polyethylene

Test voltage

3,5U0 / 5 minutes

Intensity of incomplete discharge

max. 2pC/2U0 

Max. conductor temperature for long-term load

+90°C

Max. conductor temp. at 5 sec. short circuit

+250°C

Lowest permissible cable laying temperature

-20°C

Max. conductor pulling force

30 x S (S = Al conductor cross-section in mm2) [N]

Minimum bending radius

15xD, D – cable outside diameter [mm]

Intended use

Cables intended for the transmission of electricity, for use in MV power networks with a rated voltage not exceeding U0 /U = 6/10kV; 8.7/15 kV; 12/20 kV; 18/30 kV. For laying directly in the ground, cable ducts, conduits and in the air.

Packaging

Cable reels

Reaction to fire class in accordance with EN 13501-6

Fca

  

XUHAKXS1

6/10kV

Conductor cross-section

Return wire cross-section

Rated thickness of

Approximate cable outer diameter

Approximate cable weight

Max. conductor resistance at temp.

insulation

sheath

 

 

mm2

mm2

mm

mm

kg/km

Ω/km

Ω/km

50

16

3,4

2,5

25,9

660

0,641

0,825

70

25

3,4

2,5

27,3

828

0,443

0,570

95

35

3,4

2,5

29,4

1020

0,320

0,412

120

25

3,4

2,5

30,2

1023

0,253

0,326

120

50

3,4

2,5

30,6

1245

0,253

0,326

150

25

3,4

2,5

31,9

1140

0,206

0,265

150

50

3,4

2,5

32,4

1365

0,206

0,265

185

25

3,4

2,5

33,4

1270

0,164

0,211

185

50

3,4

2,5

33,9

1494

0,164

0,211

240

25

3,4

2,5

35,8

1470

0,125

0,161

240

50

3,4

2,5

36,3

1693

0,125

0,161

300

25

3,4

2,5

37,8

1670

0,100

0,129

300

50

3,4

2,5

38,3

1892

0,100

0,129

400

50

3,4

2,5

41,0

2220

0,0778

0,100

500

50

3,4

2,5

44,0

2553

0,0605

0,078

630

50

3,4

2,6

48,3

3000

0,0469

0,060

800

50

3,4

2,7

52,1

3564

0,0367

0,047

*By agreement between the parties, the cables can be manufactured with a return wire of a different cross-section than that shown in the table.

 

XUHAKXS1

8,7/15kV

Conductor cross-section

Return wire cross-section

Rated thickness of

Approximate cable outer diameter

Approximate cable weight

Max. conductor resistance at temp.

insulation

sheath

 

 

mm2

mm2

mm

mm

kg/km

Ω/km

Ω/km

50

16

4,5

2,5

28,0

730

0,641

0,825

70

25

4,5

2,5

29,5

904

0,443

0,570

95

35

4,5

2,5

31,6

1101

0,320

0,412

120

25

4,5

2,5

32,4

1108

0,253

0,326

120

50

4,5

2,5

32,8

1333

0,253

0,326

150

25

4,5

2,5

34,1

1231

0,206

0,265

150

50

4,5

2,5

34,6

1455

0,206

0,265

185

25

4,5

2,5

35,6

1364

0,164

0,211

185

50

4,5

2,5

36,1

1590

0,164

0,211

240

25

4,5

2,5

38,0

1572

0,125

0,161

240

50

4,5

2,5

38,5

1796

0,125

0,161

300

25

4,5

2,5

40,0

1779

0,100

0,129

300

50

4,5

2,5

40,5

2004

0,100

0,129

400

50

4,5

2,5

43,2

2338

0,0778

0,100

500

50

4,5

2,5

46,2

2681

0,0605

0,078

630

50

4,5

2,6

50,7

3157

0,0469

0,060

800

50

4,5

2,8

54,5

3734

0,0367

0,047

*By agreement between the parties, the cables can be manufactured with a return wire of a different cross-section than that shown in the table.

 

XUHAKXS1

12/20kV

Conductor cross-section

Return wire cross-section

Rated thickness of

Approximate cable outer diameter

Approximate cable weight

Max. conductor resistance at temp.

insulation

sheath

 

 

mm2

mm2

mm

mm

kg/km

Ω/km

Ω/km

50

16

5,5

2,5

30,2

824

0,641

0,825

70

25

5,5

2,5

31,7

1004

0,443

0,570

95

35

5,5

2,5

33,8

1210

0,320

0,412

120

25

5,5

2,5

34,6

1219

0,253

0,326

120

50

5,5

2,5

35,1

1450

0,253

0,326

150

25

5,5

2,5

36,3

1347

0,206

0,265

150

50

5,5

2,5

36,8

1577

0,206

0,265

185

25

5,5

2,5

37,8

1486

0,164

0,211

185

50

5,5

2,5

38,3

1715

0,164

0,211

240

25

5,5

2,5

40,2

1700

0,125

0,161

240

50

5,5

2,5

40,7

1930

0,125

0,161

300

25

5,5

2,5

42,2

1914

0,100

0,129

300

50

5,5

2,5

42,7

2145

0,100

0,129

400

50

5,5

2,5

45,4

2488

0,0778

0,100

500

50

5,5

2,6

48,4

2842

0,0605

0,078

630

50

5,5

2,7

53,1

3412

0,0469

0,060

800

50

5,5

2,9

57,0

3960

0,0367

0,047

*By agreement between the parties, the cables can be manufactured with a return wire of a different cross-section than that shown in the table.

 

XUHAKXS1

18/30kV

Conductor cross-section

Return wire cross-section

Rated thickness of

Approximate cable outer diameter

Approximate cable weight

Max. conductor resistance at temp.

insulation

sheath

 

 

mm2

mm2

mm

mm

kg/km

Ω/km

Ω/km

50

16

8,0

2,5

35,0

1026

0,641

0,825

70

25

8,0

2,5

36,5

1216

0,443

0,570

95

35

8,0

2,5

38,6

1430

0,320

0,412

120

25

8,0

2,5

39,4

1450

0,253

0,326

120

50

8,0

2,5

39,8

1675

0,253

0,326

150

25

8,0

2,5

41,1

1588

0,206

0,265

150

50

8,0

2,5

41,6

1817

0,206

0,265

185

25

8,0

2,5

42,6

1737

0,164

0,211

185

50

8,0

2,5

43,1

1965

0,164

0,211

240

25

8,0

2,5

45,0

1968

0,125

0,161

240

50

8,0

2,5

45,5

2195

0,125

0,161

300

25

8,0

2,5

47,0

2195

0,100

0,129

300

50

8,0

2,5

47,5

2419

0,100

0,129

400

50

8,0

2,6

50,2

2780

0,0778

0,100

500

50

8,0

2,8

53,4

3167

0,0605

0,078

630

50

8,0

2,9

57,9

3690

0,0469

0,060

800

50

8,0

3,1

62,0

4325

0,0367

0,047

*By agreement between the parties, the cables can be manufactured with a return wire of a different cross-section than that shown in the table.

 

Warianty / Variants (51)

IDWariantSymbolPDF
30564XUHAKXS 18/30kV 1x800/50XUHAKXS1 6/10kV; 8,7/15kV; 12/20kV; 18/30kV

Wydruk obejmuje opis rodziny i widoczną stronę wariantów. Pełny zestaw można przeglądać kolejnymi stronami.