HDGsekwf(żo) PH90 300/500 V

Power cable with single-wire copper conductors (D) with silicone rubber insulation (Gs) and halogen-free material sheath (H), with or without a green-yellow protective conductor (żo), in a common aluminium foil shield (ekwf).
|
CONSTRUCTION: |
|
|
Conductors |
copper single-wire class 1,to PN-EN 60228 |
|
Insulation |
special ceramisation silicon |
|
Insulation colour |
HDGsekwf 2-conductor: blue, brown 3-conductor: black, brown, grey or blue, brown, black 4-conductor: blue, brown, black, grey 5-conductor: blue, brown, black, grey, black more than 5 conductors - in each layer: brown (metering conductor), blue (directional conductor) and other conductors - the same colours except for green-yellow, brown and blue HDGsekwf(żo) 3-conductor: green-yellow, blue, brown 4-conductor: yellow-green, black, brown, grey or yellow-green, blue, brown, black 5-conductor: green-yellow, blue, brown, black, grey more than 5 conductors - in the external layer: green-yellow (metering conductor), blue (direc- tional conductor) and other conductors - the same colours except for green-yellow, brown and blue in other layers: brown (metering conductor), blue (directional conductor) and other conductors - the same colours except for green-yellow, brown and blue |
|
Shield |
aluminium-polyester tape with an earthing conductor (HDGsekwf, HDGsekwf(żo) |
|
Sheath |
special halogen-free, self-extinguishing, flame-retardant, red colour |
|
Operating temperature |
od -30⁰C do +80⁰C |
|
Rated voltage |
300/500 V |
|
Bending radius |
10 x conductor outer diameter |
|
Application
|
halogen-free fire-resistant cables used in locations requiring equipment operation during fire; recommended for emergency illumination, smoke removal, signalling, DSO, control, fire signalling systems and fire-fighting automation systems as well as other systems ensuring safety in fire conditions; in fire conditions, such cables ensure correct operation of equipment for at least 90 minutes (PH90) and insulation durability for 180 minutes (FE180); no emission of toxic, suffocating gases and thick smoke during combustion; suitable for permanent installation inside buildings |
|
Test |
resistance of a single cable to flame propagation (fire resistance): PN-EN 60332-1, IEC 60332-1, DIN-VDE 0482-332-1 cable installation function maintenance- E30: DIN-VDE 4102-12 insulation resistance to long-term fire impact (insulation durability) FE180: IEC 60331-11, IEC 60331-21, IEC 60331-31, DIN-VDE 0472-814 resistance of a cable bundle to flame propagation PN-EN 60332-3-24, IEC 60332-3, DIN-VDE 482-266-2 emission of corrosive gases during combustion: PN-EN 50267, IEC 60754-2, DIN-VDE 0472-813 emission of smoke density during combustion: PN-EN 61034-1(-2), IEC 61034-1(-2), DIN-VDE 0482-1034-2 |
|
Packing |
coils, drums |
|
HDGsekwf(żo) PH90 300/500 V |
||
|
Conductor number and rated cross-section [n x mm2] |
Approximate external cable diameter [mm] |
Approximate cable weight [kg/km] |
|
2 x 1,0 |
7,1 |
63 |
|
2 x 1,5 |
7,9 |
78 |
|
2 x 2,5 |
9,5 |
115 |
|
2 x 4,0 |
10,4 |
150 |
|
3 x 1,0 |
7,5 |
79 |
|
3 x 1,5 |
8,3 |
99 |
|
3 x 2,5 |
10,0 |
148 |
|
3 x 4,0 |
11,2 |
203 |
|
4 x 1,0 |
8,4 |
100 |
|
4 x 1,5 |
9,5 |
132 |
|
4 x 2,5 |
11,2 |
190 |
|
4 x 4,0 |
12,3 |
256 |
|
5 x 1,0 |
9,1 |
125 |
|
5 x 1,5 |
10,2 |
161 |
|
5 x 2,5 |
12,0 |
235 |
|
5 x 4,0 |
13,3 |
318 |
|
7 x 1,0 |
9,9 |
154 |
|
7 x 1,5 |
11,3 |
203 |
|
7 x 2,5 |
13,1 |
293 |
|
10 x 1,0 |
12,4 |
214 |
|
10 x 1,5 |
14,0 |
279 |
|
10 x 2,5 |
17,0 |
430 |
|
12 x 1,0 |
12,8 |
244 |
|
12 x 1,5 |
14,4 |
320 |
|
12 x 2,5 |
17,5 |
494 |
|
14 x 1,0 |
13,4 |
276 |
|
14 x 1,5 |
15,1 |
371 |
|
14 x 2,5 |
18,4 |
589 |
|
16 x 1,0 |
14,2 |
313 |
|
16 x 1,5 |
16,5 |
438 |
|
16 x 2,5 |
20,0 |
668 |
|
19 x 1,0 |
14,8 |
375 |
|
19 x 1,5 |
17,4 |
520 |
|
19 x 2,5 |
21,0 |
758 |
|
20 x 1,0 |
16,2 |
408 |
|
20 x 1,5 |
18,9 |
565 |
|
20 x 2,5 |
22,1 |
825 |
|
24 x 1,0 |
17,7 |
462 |
|
24 x 1,5 |
20,7 |
642 |
|
24 x 2,5 |
24,9 |
976 |
|
30 x 1,0 |
19,3 |
580 |
|
30 x 1,5 |
21,8 |
768 |
|
30 x 2,5 |
26,3 |
1173 |
|
37 x 1,0 |
20,7 |
689 |
|
37 x 1,5 |
24,1 |
918 |
|
37 x 2,5 |
28,3 |
1406 |
Warianty / Variants (88)
| ID | Wariant | Symbol | |
|---|---|---|---|
| 15407 | HDGekwfżo PH90 4x1 300/500V | HDGsekwf(żo) PH90 300/500 V | |
| 15408 | HDGsekwfżo PH90 4x1,5 300/500V | HDGsekwf(żo) PH90 300/500 V | |
| 15409 | HDGsekwfżo PH90 4x2,5 300/500V | HDGsekwf(żo) PH90 300/500 V | |
| 15410 | HDGsekwfżo PH90 4x4 300/500V | HDGsekwf(żo) PH90 300/500 V | |
| 15411 | HDGsekwfżo PH90 5x1 300/500V | HDGsekwf(żo) PH90 300/500 V | |
| 15412 | HDGsekwfżo PH90 5x1,5 300/500V | HDGsekwf(żo) PH90 300/500 V | |
| 15413 | HDGsekwfżo PH90 5x2,5 300/500V | HDGsekwf(żo) PH90 300/500 V | |
| 15414 | HDGsekwfżo PH90 5x4 300/500V | HDGsekwf(żo) PH90 300/500 V | |
| 15415 | HDGsekwfżo PH90 7x1 300/500V | HDGsekwf(żo) PH90 300/500 V | |
| 15416 | HDGsekwfżo PH90 7x1,5 300/500V | HDGsekwf(żo) PH90 300/500 V | |
| 15417 | HDGsekwfżo PH90 7x2,5 300/500V | HDGsekwf(żo) PH90 300/500 V | |
| 15418 | HDGsekwfżo PH90 10x1 300/500V | HDGsekwf(żo) PH90 300/500 V | |
| 15419 | HDGsekwfżo PH90 10x1,5 300/500V | HDGsekwf(żo) PH90 300/500 V | |
| 15420 | HDGsekwfżo PH90 10x2,5 300/500V | HDGsekwf(żo) PH90 300/500 V | |
| 15421 | HDGsekwfżo PH90 12x1 300/500V | HDGsekwf(żo) PH90 300/500 V | |
| 15422 | HDGsekwfżo PH90 12x1,5 300/500V | HDGsekwf(żo) PH90 300/500 V | |
| 15423 | HDGsekwfżo PH90 12x2,5 300/500V | HDGsekwf(żo) PH90 300/500 V | |
| 15424 | HDGsekwfżo PH90 14x1 300/500V | HDGsekwf(żo) PH90 300/500 V | |
| 15425 | HDGsekwfżo PH90 14x1,5 300/500V | HDGsekwf(żo) PH90 300/500 V | |
| 15426 | HDGsekwfżo PH90 14x2,5 300/500V | HDGsekwf(żo) PH90 300/500 V | |
| 15427 | HDGsekwfżo PH90 16x1 300/500V | HDGsekwf(żo) PH90 300/500 V | |
| 15428 | HDGsekwfżo PH90 16x1,5 300/500V | HDGsekwf(żo) PH90 300/500 V | |
| 15429 | HDGsekwfżo PH90 16x2,5 300/500V | HDGsekwf(żo) PH90 300/500 V | |
| 15430 | HDGsekwfżo PH90 19x1 300/500V | HDGsekwf(żo) PH90 300/500 V | |
| 15431 | HDGsekwfżo PH90 19x1,5 300/500V | HDGsekwf(żo) PH90 300/500 V | |
| 15432 | HDGsekwfżo PH90 19x2,5 300/500V | HDGsekwf(żo) PH90 300/500 V | |
| 15433 | HDGsekwfżo PH90 20x1 300/500V | HDGsekwf(żo) PH90 300/500 V | |
| 15434 | HDGsekwfżo PH90 20x1,5 300/500V | HDGsekwf(żo) PH90 300/500 V | |
| 15435 | HDGsekwfżo PH90 20x2,5 300/500V | HDGsekwf(żo) PH90 300/500 V | |
| 15436 | HDGsekwfżo PH90 24x1 300/500V | HDGsekwf(żo) PH90 300/500 V | |
| 15437 | HDGsekwfżo PH90 24x1,5 300/500V | HDGsekwf(żo) PH90 300/500 V | |
| 15438 | HDGsekwfżo PH90 24x2,5 300/500V | HDGsekwf(żo) PH90 300/500 V | |
| 15439 | HDGsekwfżo PH90 30x1 300/500V | HDGsekwf(żo) PH90 300/500 V | |
| 15440 | HDGsekwfżo PH90 30x1,5 300/500V | HDGsekwf(żo) PH90 300/500 V | |
| 15441 | HDGsekwfżo PH90 30x2,5 300/500V | HDGsekwf(żo) PH90 300/500 V | |
| 15442 | HDGsekwfżo PH90 37x1 300/500V | HDGsekwf(żo) PH90 300/500 V | |
| 15443 | HDGsekwfżo PH90 37x1,5 300/500V | HDGsekwf(żo) PH90 300/500 V | |
| 15444 | HDGsekwfżo PH90 37x2,5 300/500V | HDGsekwf(żo) PH90 300/500 V |