YHAKXS1 6/10kV; 8,7/15kV; 12/20kV; 18/30kV

YHAKXS1 6/10kV; 8,7/15kV; 12/20kV; 18/30kV

Single-conductor power cables (K) with aluminium (A) conductor with radial field (H), with normal thickness (1) cross-linked polyethylene (XS) insulation with coaxial copper return wire and softened PVC (Y) sheath.

DESIGN

Standard

PN-HD 620 S3:2023-04 part 0, 1 and 10R

Conductor

Aluminium multi-stranded, round of class 2

Shield on the conductor

Semi-conductive polyethylene

Insulation

Cross-linked polyethylene

Shield on the insulation

Semi-conductive polyethylene

Shield wrapping

Semi-conductive tape

Return wire

Copper wires, round + spiral copper tape

Return wire wrapping

Polyester tape

Sheath

Softened PVC

Test voltage

3.5U0 / 5 minutes

Intensity of incomplete discharge

max. 2pC/2U0 

Max. conductor temperature for long-term load

+90°C

Max. conductor temp. at 5 sec. short circuit

+250°C

Lowest permissible cable laying temperature

-5°C

Max. conductor pulling force

30 x S (S = Al conductor cross-section in mm2) [N]

Minimum bending radius

15xD, D – cable outside diameter [mm]

Intended use

Cables intended for the transmission of electricity, for use in MV power networks with a rated voltage not exceeding U0/U = 6/10kV; 8.7/15 kV; 12/20 kV; 18/30 kV. For laying directly in the ground, cable ducts, conduits and in the air.

Packaging

Cable reels

Reaction to fire class in accordance with EN 13501-6

Eca

 

YHAKXS1

6/10kV

Conductor cross-section

Return wire cross-section

Rated thickness of

Approximate cable outer diameter

Approximate cable weight

Max. conductor resistance at temp.

insulation

sheath

20˚C

90˚C

mm2

mm2

mm

mm

kg/km

Ω/km

Ω/km

50

16

3,4

2,5

25,3

757

0,641

0,825

70

25

3,4

2,5

26,9

937

0,443

0,570

95

35

3,4

2,5

28,9

1141

0,320

0,412

120

25

3,4

2,5

29,9

1151

0,253

0,326

120

50

3,4

2,5

30,3

1383

0,253

0,326

150

25

3,4

2,5

31,6

1275

0,206

0,265

150

50

3,4

2,5

32,0

1508

0,206

0,265

185

25

3,4

2,5

33,1

1412

0,164

0,211

185

50

3,4

2,5

33,5

1644

0,164

0,211

240

25

3,4

2,5

35,5

1620

0,125

0,161

240

50

3,4

2,5

35,9

1855

0,125

0,161

300

25

3,4

2,5

37,5

1833

0,100

0,129

300

50

3,4

2,5

37,9

2065

0,100

0,129

400

50

3,4

2,5

40,6

2400

0,0778

0,100

500

50

3,4

2,5

43,6

2724

0,0605

0,078

630

50

3,4

2,6

48,4

3324

0,0469

0,060

800

50

3,4

2,7

51,6

3842

0,0367

0,047

*By agreement between the parties, the cables can be manufactured with a return wire of a different cross-section than that shown in the table.

 

YHAKXS1

8,7/15kV

Conductor cross-section

Return wire cross-section

Rated thickness of

Approximate cable outer diameter

Approximate cable weight

Max. conductor resistance at temp.

insulation

sheath

20˚C

90˚C

mm2

mm2

mm

mm

kg/km

Ω/km

Ω/km

50

16

4,5

2,5

27,4

815

0,641

0,825

70

25

4,5

2,5

28,9

994

0,443

0,570

95

35

4,5

2,5

30,9

1198

0,320

0,412

120

25

4,5

2,5

31,8

1208

0,253

0,326

120

50

4,5

2,5

32,2

1434

0,253

0,326

150

25

4,5

2,5

33,7

1341

0,206

0,265

150

50

4,5

2,5

34,1

1567

0,206

0,265

185

25

4,5

2,5

35,2

1480

0,164

0,211

185

50

4,5

2,5

35,6

1705

0,164

0,211

240

25

4,5

2,5

37,3

1685

0,125

0,161

240

50

4,5

2,5

37,7

1911

0,125

0,161

300

25

4,5

2,5

39,8

1913

0,100

0,129

300

50

4,5

2,5

40,2

2140

0,100

0,129

400

50

4,5

2,5

42,5

2470

0,0778

0,100

500

50

4,5

2,5

46,2

2842

0,0605

0,078

630

50

4,5

2,6

50,3

3328

0,0469

0,060

800

50

4,5

2,8

53,8

3924

0,0367

0,047

*By agreement between the parties, the cables can be manufactured with a return wire of a different cross-section than that shown in the table.

 

YHAKXS1

12/20kV

Conductor cross-section

Return wire cross-section

Rated thickness of

Approximate cable outer diameter

Approximate cable weight

Max. conductor resistance at temp.

insulation

sheath

20˚C

90˚C

mm2

mm2

mm

mm

kg/km

Ω/km

Ω/km

50

16

5,5

2,5

29,5

934

0,641

0,825

70

25

5,5

2,5

31,2

1127

0,443

0,570

95

35

5,5

2,5

33,0

1337

0,320

0,412

120

25

5,5

2,5

34,0

1356

0,253

0,326

120

50

5,5

2,5

34,5

1587

0,253

0,326

150

25

5,5

2,5

35,8

1490

0,206

0,265

150

50

5,5

2,5

36,1

1717

0,206

0,265

185

25

5,5

2,5

37,2

1630

0,164

0,211

185

50

5,5

2,5

37,6

1860

0,164

0,211

240

25

5,5

2,5

39,6

1855

0,125

0,161

240

50

5,5

2,5

40,1

2090

0,125

0,161

300

25

5,5

2,5

41,6

2078

0,100

0,129

300

50

5,5

2,5

42,0

2310

0,100

0,129

400

50

5,5

2,5

44,7

2665

0,0778

0,100

500

50

5,5

2,6

47,7

3032

0,0605

0,078

630

50

5,5

2,7

52,0

3527

0,0469

0,060

800

50

5,5

2,9

55,3

4093

0,0367

0,047

*By agreement between the parties, the cables can be manufactured with a return wire of a different cross-section than that shown in the table.

 

YHAKXS1

18/30kV

Conductor cross-section

Return wire cross-section

Rated thickness of

Approximate cable outer diameter

Approximate cable weight

Max. conductor resistance at temp.

insulation

sheath

20˚C

90˚C

mm2

mm2

mm

mm

kg/km

Ω/km

Ω/km

50

16

8,0

2,5

34,7

1181

0,641

0,825

70

25

8,0

2,5

36,2

1356

0,443

0,570

95

35

8,0

2,5

38,2

1580

0,320

0,412

120

25

8,0

2,5

39,1

1600

0,253

0,326

120

50

8,0

2,5

39,5

1833

0,253

0,326

150

25

8,0

2,5

40,8

1748

0,206

0,265

150

50

8,0

2,5

41,2

1963

0,206

0,265

185

25

8,0

2,5

42,3

1902

0,164

0,211

185

50

8,0

2,5

42,7

2134

0,164

0,211

240

25

8,0

2,5

44,7

2143

0,125

0,161

240

50

8,0

2,5

45,1

2356

0,125

0,161

300

25

8,0

2,5

46,7

2379

0,100

0,129

300

50

8,0

2,5

47,1

2610

0,100

0,129

400

50

8,0

2,6

49,8

2983

0,0778

0,100

500

50

8,0

2,8

52,8

3368

0,0605

0,078

630

50

8,0

2,9

57,2

3920

0,0469

0,060

800

50

8,0

3,1

61,3

4590

0,0367

0,047

*By agreement between the parties, the cables can be manufactured with a return wire of a different cross-section than that shown in the table.

  

Warianty / Variants (51)

IDWariantSymbolPDF
30353YHAKXS 6/10kV 1x35/16YHAKXS1 6/10kV; 8,7/15kV; 12/20kV; 18/30kV
30415YHAKXS 6/10kV 1x50/16YHAKXS1 6/10kV; 8,7/15kV; 12/20kV; 18/30kV
30416YHAKXS 6/10kV 1x70/25YHAKXS1 6/10kV; 8,7/15kV; 12/20kV; 18/30kV
30417YHAKXS 6/10kV 1x95/35YHAKXS1 6/10kV; 8,7/15kV; 12/20kV; 18/30kV
30418YHAKXS 6/10kV 1x120/50YHAKXS1 6/10kV; 8,7/15kV; 12/20kV; 18/30kV
30419YHAKXS 6/10kV 1x150/50YHAKXS1 6/10kV; 8,7/15kV; 12/20kV; 18/30kV
30420YHAKXS 6/10kV 1x185/50YHAKXS1 6/10kV; 8,7/15kV; 12/20kV; 18/30kV
30421YHAKXS 6/10kV 1x240/50YHAKXS1 6/10kV; 8,7/15kV; 12/20kV; 18/30kV
30422YHAKXS 6/10kV 1x300/50YHAKXS1 6/10kV; 8,7/15kV; 12/20kV; 18/30kV
30423YHAKXS 6/10kV 1x400/50YHAKXS1 6/10kV; 8,7/15kV; 12/20kV; 18/30kV
30424YHAKXS 6/10kV 1x500/50YHAKXS1 6/10kV; 8,7/15kV; 12/20kV; 18/30kV
30425YHAKXS 6/10kV 1x630/50YHAKXS1 6/10kV; 8,7/15kV; 12/20kV; 18/30kV
30426YHAKXS 6/10kV 1x800/50YHAKXS1 6/10kV; 8,7/15kV; 12/20kV; 18/30kV
30427YHAKXS 8,7/15kV 1x35/16YHAKXS1 6/10kV; 8,7/15kV; 12/20kV; 18/30kV
30428YHAKXS 8,7/15kV 1x50/16YHAKXS1 6/10kV; 8,7/15kV; 12/20kV; 18/30kV
30429YHAKXS 8,7/15kV 1x70/25YHAKXS1 6/10kV; 8,7/15kV; 12/20kV; 18/30kV
30430YHAKXS 8,7/15kV 1x95/35YHAKXS1 6/10kV; 8,7/15kV; 12/20kV; 18/30kV
30431YHAKXS 8,7/15kV 1x120/50YHAKXS1 6/10kV; 8,7/15kV; 12/20kV; 18/30kV
30432YHAKXS 8,7/15kV 1x150/50YHAKXS1 6/10kV; 8,7/15kV; 12/20kV; 18/30kV
30433YHAKXS 8,7/15kV 1x185/50YHAKXS1 6/10kV; 8,7/15kV; 12/20kV; 18/30kV
30434YHAKXS 8,7/15kV 1x240/50YHAKXS1 6/10kV; 8,7/15kV; 12/20kV; 18/30kV
30435YHAKXS 8,7/15kV 1x300/50YHAKXS1 6/10kV; 8,7/15kV; 12/20kV; 18/30kV
30436YHAKXS 8,7/15kV 1x400/50YHAKXS1 6/10kV; 8,7/15kV; 12/20kV; 18/30kV
30437YHAKXS 8,7/15kV 1x500/50YHAKXS1 6/10kV; 8,7/15kV; 12/20kV; 18/30kV
30438YHAKXS 8,7/15kV 1x630/50YHAKXS1 6/10kV; 8,7/15kV; 12/20kV; 18/30kV
30439YHAKXS 8,7/15kV 1x800/50YHAKXS1 6/10kV; 8,7/15kV; 12/20kV; 18/30kV
30440YHAKXS 12/20kV 1x35/16YHAKXS1 6/10kV; 8,7/15kV; 12/20kV; 18/30kV
30441YHAKXS 12/20kV 1x50/16YHAKXS1 6/10kV; 8,7/15kV; 12/20kV; 18/30kV
30442YHAKXS 12/20kV 1x70/25YHAKXS1 6/10kV; 8,7/15kV; 12/20kV; 18/30kV
30443YHAKXS 12/20kV 1x95/35YHAKXS1 6/10kV; 8,7/15kV; 12/20kV; 18/30kV
30444YHAKXS 12/20kV 1x120/50YHAKXS1 6/10kV; 8,7/15kV; 12/20kV; 18/30kV
30445YHAKXS 12/20kV 1x150/50YHAKXS1 6/10kV; 8,7/15kV; 12/20kV; 18/30kV
30446YHAKXS 12/20kV 1x185/50YHAKXS1 6/10kV; 8,7/15kV; 12/20kV; 18/30kV
30447YHAKXS 12/20kV 1x240/50YHAKXS1 6/10kV; 8,7/15kV; 12/20kV; 18/30kV
30448YHAKXS 12/20kV 1x300/50YHAKXS1 6/10kV; 8,7/15kV; 12/20kV; 18/30kV
30449YHAKXS 12/20kV 1x400/50YHAKXS1 6/10kV; 8,7/15kV; 12/20kV; 18/30kV
30450YHAKXS 12/20kV 1x500/50YHAKXS1 6/10kV; 8,7/15kV; 12/20kV; 18/30kV
30451YHAKXS 12/20kV 1x630/50YHAKXS1 6/10kV; 8,7/15kV; 12/20kV; 18/30kV
30452YHAKXS 12/20kV 1x800/50YHAKXS1 6/10kV; 8,7/15kV; 12/20kV; 18/30kV
30453YHAKXS 18/30kV 1x50/16YHAKXS1 6/10kV; 8,7/15kV; 12/20kV; 18/30kV
30454YHAKXS 18/30kV 1x70/25YHAKXS1 6/10kV; 8,7/15kV; 12/20kV; 18/30kV
30455YHAKXS 18/30kV 1x95/35YHAKXS1 6/10kV; 8,7/15kV; 12/20kV; 18/30kV
30456YHAKXS 18/30kV 1x120/50YHAKXS1 6/10kV; 8,7/15kV; 12/20kV; 18/30kV
30457YHAKXS 18/30kV 1x150/50YHAKXS1 6/10kV; 8,7/15kV; 12/20kV; 18/30kV
30458YHAKXS 18/30kV 1x185/50YHAKXS1 6/10kV; 8,7/15kV; 12/20kV; 18/30kV
30459YHAKXS 18/30kV 1x240/50YHAKXS1 6/10kV; 8,7/15kV; 12/20kV; 18/30kV
30460YHAKXS 18/30kV 1x300/50YHAKXS1 6/10kV; 8,7/15kV; 12/20kV; 18/30kV
30461YHAKXS 18/30kV 1x400/50YHAKXS1 6/10kV; 8,7/15kV; 12/20kV; 18/30kV
30462YHAKXS 18/30kV 1x500/50YHAKXS1 6/10kV; 8,7/15kV; 12/20kV; 18/30kV
30463YHAKXS 18/30kV 1x630/50YHAKXS1 6/10kV; 8,7/15kV; 12/20kV; 18/30kV

Wydruk obejmuje opis rodziny i widoczną stronę wariantów. Pełny zestaw można przeglądać kolejnymi stronami.