XUHAKXS1 6/10kV; 8,7/15kV; 12/20kV; 18/30kV

Single-conductor power cables (K) with aluminium (A) conductor with radial field (H), with normal thickness (1) cross-linked polyethylene (XS) insulation with coaxial copper return wire sealed longitudinally (U) and thermoplastic polyethylene (X) sheath.
|
DESIGN |
|
|
Standard |
PN-HD 620 S3:2023-04 part 0, 1 and 10R |
|
Conductor |
Aluminium multi-stranded, round of class 2 |
|
Shield on the conductor |
Semi-conductive polyethylene |
|
Insulation |
Cross-linked polyethylene |
|
Shield on the insulation |
Semi-conductive polyethylene |
|
Shield wrapping |
Semi-conductive water blocking tape |
|
Return wire |
Copper wires, round + spiral copper tape |
|
Return wire wrapping |
Non-conductive water blocking tape |
|
Sheath |
Polyethylene |
|
Test voltage |
3,5U0 / 5 minutes |
|
Intensity of incomplete discharge |
max. 2pC/2U0 |
|
Max. conductor temperature for long-term load |
+90°C |
|
Max. conductor temp. at 5 sec. short circuit |
+250°C |
|
Lowest permissible cable laying temperature |
-20°C |
|
Max. conductor pulling force |
30 x S (S = Al conductor cross-section in mm2) [N] |
|
Minimum bending radius |
15xD, D – cable outside diameter [mm] |
|
Intended use |
Cables intended for the transmission of electricity, for use in MV power networks with a rated voltage not exceeding U0 /U = 6/10kV; 8.7/15 kV; 12/20 kV; 18/30 kV. For laying directly in the ground, cable ducts, conduits and in the air. |
|
Packaging |
Cable reels |
|
Reaction to fire class in accordance with EN 13501-6 |
Fca |
|
XUHAKXS1 6/10kV |
|||||||
|
Conductor cross-section |
Return wire cross-section |
Rated thickness of |
Approximate cable outer diameter |
Approximate cable weight |
Max. conductor resistance at temp. |
||
|
insulation |
sheath |
|
|
||||
|
mm2 |
mm2 |
mm |
mm |
kg/km |
Ω/km |
Ω/km |
|
|
50 |
16 |
3,4 |
2,5 |
25,9 |
660 |
0,641 |
0,825 |
|
70 |
25 |
3,4 |
2,5 |
27,3 |
828 |
0,443 |
0,570 |
|
95 |
35 |
3,4 |
2,5 |
29,4 |
1020 |
0,320 |
0,412 |
|
120 |
25 |
3,4 |
2,5 |
30,2 |
1023 |
0,253 |
0,326 |
|
120 |
50 |
3,4 |
2,5 |
30,6 |
1245 |
0,253 |
0,326 |
|
150 |
25 |
3,4 |
2,5 |
31,9 |
1140 |
0,206 |
0,265 |
|
150 |
50 |
3,4 |
2,5 |
32,4 |
1365 |
0,206 |
0,265 |
|
185 |
25 |
3,4 |
2,5 |
33,4 |
1270 |
0,164 |
0,211 |
|
185 |
50 |
3,4 |
2,5 |
33,9 |
1494 |
0,164 |
0,211 |
|
240 |
25 |
3,4 |
2,5 |
35,8 |
1470 |
0,125 |
0,161 |
|
240 |
50 |
3,4 |
2,5 |
36,3 |
1693 |
0,125 |
0,161 |
|
300 |
25 |
3,4 |
2,5 |
37,8 |
1670 |
0,100 |
0,129 |
|
300 |
50 |
3,4 |
2,5 |
38,3 |
1892 |
0,100 |
0,129 |
|
400 |
50 |
3,4 |
2,5 |
41,0 |
2220 |
0,0778 |
0,100 |
|
500 |
50 |
3,4 |
2,5 |
44,0 |
2553 |
0,0605 |
0,078 |
|
630 |
50 |
3,4 |
2,6 |
48,3 |
3000 |
0,0469 |
0,060 |
|
800 |
50 |
3,4 |
2,7 |
52,1 |
3564 |
0,0367 |
0,047 |
|
*By agreement between the parties, the cables can be manufactured with a return wire of a different cross-section than that shown in the table. |
|||||||
|
XUHAKXS1 8,7/15kV |
|||||||
|
Conductor cross-section |
Return wire cross-section |
Rated thickness of |
Approximate cable outer diameter |
Approximate cable weight |
Max. conductor resistance at temp. |
||
|
insulation |
sheath |
|
|
||||
|
mm2 |
mm2 |
mm |
mm |
kg/km |
Ω/km |
Ω/km |
|
|
50 |
16 |
4,5 |
2,5 |
28,0 |
730 |
0,641 |
0,825 |
|
70 |
25 |
4,5 |
2,5 |
29,5 |
904 |
0,443 |
0,570 |
|
95 |
35 |
4,5 |
2,5 |
31,6 |
1101 |
0,320 |
0,412 |
|
120 |
25 |
4,5 |
2,5 |
32,4 |
1108 |
0,253 |
0,326 |
|
120 |
50 |
4,5 |
2,5 |
32,8 |
1333 |
0,253 |
0,326 |
|
150 |
25 |
4,5 |
2,5 |
34,1 |
1231 |
0,206 |
0,265 |
|
150 |
50 |
4,5 |
2,5 |
34,6 |
1455 |
0,206 |
0,265 |
|
185 |
25 |
4,5 |
2,5 |
35,6 |
1364 |
0,164 |
0,211 |
|
185 |
50 |
4,5 |
2,5 |
36,1 |
1590 |
0,164 |
0,211 |
|
240 |
25 |
4,5 |
2,5 |
38,0 |
1572 |
0,125 |
0,161 |
|
240 |
50 |
4,5 |
2,5 |
38,5 |
1796 |
0,125 |
0,161 |
|
300 |
25 |
4,5 |
2,5 |
40,0 |
1779 |
0,100 |
0,129 |
|
300 |
50 |
4,5 |
2,5 |
40,5 |
2004 |
0,100 |
0,129 |
|
400 |
50 |
4,5 |
2,5 |
43,2 |
2338 |
0,0778 |
0,100 |
|
500 |
50 |
4,5 |
2,5 |
46,2 |
2681 |
0,0605 |
0,078 |
|
630 |
50 |
4,5 |
2,6 |
50,7 |
3157 |
0,0469 |
0,060 |
|
800 |
50 |
4,5 |
2,8 |
54,5 |
3734 |
0,0367 |
0,047 |
|
*By agreement between the parties, the cables can be manufactured with a return wire of a different cross-section than that shown in the table. |
|||||||
|
XUHAKXS1 12/20kV |
|||||||
|
Conductor cross-section |
Return wire cross-section |
Rated thickness of |
Approximate cable outer diameter |
Approximate cable weight |
Max. conductor resistance at temp. |
||
|
insulation |
sheath |
|
|
||||
|
mm2 |
mm2 |
mm |
mm |
kg/km |
Ω/km |
Ω/km |
|
|
50 |
16 |
5,5 |
2,5 |
30,2 |
824 |
0,641 |
0,825 |
|
70 |
25 |
5,5 |
2,5 |
31,7 |
1004 |
0,443 |
0,570 |
|
95 |
35 |
5,5 |
2,5 |
33,8 |
1210 |
0,320 |
0,412 |
|
120 |
25 |
5,5 |
2,5 |
34,6 |
1219 |
0,253 |
0,326 |
|
120 |
50 |
5,5 |
2,5 |
35,1 |
1450 |
0,253 |
0,326 |
|
150 |
25 |
5,5 |
2,5 |
36,3 |
1347 |
0,206 |
0,265 |
|
150 |
50 |
5,5 |
2,5 |
36,8 |
1577 |
0,206 |
0,265 |
|
185 |
25 |
5,5 |
2,5 |
37,8 |
1486 |
0,164 |
0,211 |
|
185 |
50 |
5,5 |
2,5 |
38,3 |
1715 |
0,164 |
0,211 |
|
240 |
25 |
5,5 |
2,5 |
40,2 |
1700 |
0,125 |
0,161 |
|
240 |
50 |
5,5 |
2,5 |
40,7 |
1930 |
0,125 |
0,161 |
|
300 |
25 |
5,5 |
2,5 |
42,2 |
1914 |
0,100 |
0,129 |
|
300 |
50 |
5,5 |
2,5 |
42,7 |
2145 |
0,100 |
0,129 |
|
400 |
50 |
5,5 |
2,5 |
45,4 |
2488 |
0,0778 |
0,100 |
|
500 |
50 |
5,5 |
2,6 |
48,4 |
2842 |
0,0605 |
0,078 |
|
630 |
50 |
5,5 |
2,7 |
53,1 |
3412 |
0,0469 |
0,060 |
|
800 |
50 |
5,5 |
2,9 |
57,0 |
3960 |
0,0367 |
0,047 |
|
*By agreement between the parties, the cables can be manufactured with a return wire of a different cross-section than that shown in the table. |
|||||||
|
XUHAKXS1 18/30kV |
|||||||
|
Conductor cross-section |
Return wire cross-section |
Rated thickness of |
Approximate cable outer diameter |
Approximate cable weight |
Max. conductor resistance at temp. |
||
|
insulation |
sheath |
|
|
||||
|
mm2 |
mm2 |
mm |
mm |
kg/km |
Ω/km |
Ω/km |
|
|
50 |
16 |
8,0 |
2,5 |
35,0 |
1026 |
0,641 |
0,825 |
|
70 |
25 |
8,0 |
2,5 |
36,5 |
1216 |
0,443 |
0,570 |
|
95 |
35 |
8,0 |
2,5 |
38,6 |
1430 |
0,320 |
0,412 |
|
120 |
25 |
8,0 |
2,5 |
39,4 |
1450 |
0,253 |
0,326 |
|
120 |
50 |
8,0 |
2,5 |
39,8 |
1675 |
0,253 |
0,326 |
|
150 |
25 |
8,0 |
2,5 |
41,1 |
1588 |
0,206 |
0,265 |
|
150 |
50 |
8,0 |
2,5 |
41,6 |
1817 |
0,206 |
0,265 |
|
185 |
25 |
8,0 |
2,5 |
42,6 |
1737 |
0,164 |
0,211 |
|
185 |
50 |
8,0 |
2,5 |
43,1 |
1965 |
0,164 |
0,211 |
|
240 |
25 |
8,0 |
2,5 |
45,0 |
1968 |
0,125 |
0,161 |
|
240 |
50 |
8,0 |
2,5 |
45,5 |
2195 |
0,125 |
0,161 |
|
300 |
25 |
8,0 |
2,5 |
47,0 |
2195 |
0,100 |
0,129 |
|
300 |
50 |
8,0 |
2,5 |
47,5 |
2419 |
0,100 |
0,129 |
|
400 |
50 |
8,0 |
2,6 |
50,2 |
2780 |
0,0778 |
0,100 |
|
500 |
50 |
8,0 |
2,8 |
53,4 |
3167 |
0,0605 |
0,078 |
|
630 |
50 |
8,0 |
2,9 |
57,9 |
3690 |
0,0469 |
0,060 |
|
800 |
50 |
8,0 |
3,1 |
62,0 |
4325 |
0,0367 |
0,047 |
|
*By agreement between the parties, the cables can be manufactured with a return wire of a different cross-section than that shown in the table. |
|||||||
Warianty / Variants (51)
| ID | Wariant | Symbol | |
|---|---|---|---|
| 30564 | XUHAKXS 18/30kV 1x800/50 | XUHAKXS1 6/10kV; 8,7/15kV; 12/20kV; 18/30kV |
Wydruk obejmuje opis rodziny i widoczną stronę wariantów. Pełny zestaw można przeglądać kolejnymi stronami.