XnUHKXS1 6/10kV; 8,7/15kV; 12/20kV; 18/30kV

Single-conductor power cables (K) with copper conductor with radial field (H), with normal thickness (1) cross-linked polyethylene (XS) insulation with coaxial copper return wire sealed longitudinally (U)with increased flame propagation resistance polyethylene (Xn) sheath.
|
DESIGN |
|
|
Standard |
PN-HD 620 S3:2023-04 part 0, 1 and 10R |
|
Conductor |
Multi-stranded copper, round grade 2 |
|
Shield on the conductor |
Semi-conductive polyethylene |
|
Insulation |
Cross-linked polyethylene |
|
Shield on the insulation |
Semi-conductive polyethylene |
|
Shield wrapping |
Semi-conductive water blocking tape |
|
Return wire |
Copper wires, round + spiral copper tape |
|
Return wire wrapping |
Non-conductive water blocking tape |
|
Sheath |
Polyethylene |
|
Test voltage |
3,5U0/ 5 minutes |
|
Intensity of incomplete discharge |
max. 2pC/2U0 |
|
Max. conductor temperature for long-term load |
+90°C |
|
Max. conductor temp. at 5 sec. short circuit |
+250°C |
|
Lowest permissible cable laying temperature |
-20°C |
|
Minimum ambient temperature for permanent cable installation |
-30°C |
|
Max. conductor pulling force |
50 x S (S = Cu conductor cross-section in mm2) [N] |
|
Minimum bending radius |
15xD, D – cable outside diameter [mm] |
|
Intended use |
Cables intended for the transmission of electricity, for use in MV power networks with a rated voltage not exceeding U0/U = 6/10kV; 8.7/15 kV; 12/20 kV; 18/30 kV. For laying directly in the ground, cable ducts, conduits and in the air. |
|
Packaging |
Cable reels |
|
Reaction to fire class in accordance with EN 13501-6 |
Eca |
|
XnUHKXS1 6/10kV |
|||||||
|
Conductor cross-section |
Return wire cross-section |
Rated thickness of |
Approximate cable outer diameter |
Approximate cable weight |
Max. conductor resistance at temp. |
||
|
insulation |
sheath |
20°C |
90°C |
||||
|
mm2 |
mm2 |
mm |
mm |
kg/km |
Ω/km |
Ω/km |
|
|
50 |
16 |
3,4 |
2,5 |
25,8 |
983 |
0,387 |
0,495 |
|
70 |
25 |
3,4 |
2,5 |
27,3 |
1278 |
0,268 |
0,343 |
|
95 |
35 |
3,4 |
2,5 |
29,4 |
1619 |
0,193 |
0,247 |
|
120 |
25 |
3,4 |
2,5 |
30,2 |
1768 |
0,153 |
0,196 |
|
120 |
50 |
3,4 |
2,5 |
30,7 |
1994 |
0,153 |
0,196 |
|
150 |
25 |
3,4 |
2,5 |
31,9 |
2066 |
0,124 |
0,159 |
|
150 |
50 |
3,4 |
2,5 |
32,4 |
2291 |
0,124 |
0,159 |
|
185 |
25 |
3,4 |
2,5 |
33,4 |
2416 |
0,0991 |
0,127 |
|
185 |
50 |
3,4 |
2,5 |
33,9 |
2642 |
0,0991 |
0,127 |
|
240 |
25 |
3,4 |
2,5 |
35,8 |
2973 |
0,0754 |
0,097 |
|
240 |
50 |
3,4 |
2,5 |
36,3 |
3200 |
0,0754 |
0,097 |
|
300 |
25 |
3,4 |
2,5 |
37,8 |
3507 |
0,0601 |
0,077 |
|
300 |
50 |
3,4 |
2,5 |
38,3 |
3732 |
0,0601 |
0,077 |
|
400 |
50 |
3,4 |
2,5 |
41,0 |
4705 |
0,0470 |
0,060 |
|
500 |
50 |
3,4 |
2,5 |
44,0 |
5651 |
0,0366 |
0,047 |
|
630 |
50 |
3,4 |
2,6 |
48,3 |
6886 |
0,0283 |
0,036 |
|
800 |
50 |
3,4 |
2,7 |
52,1 |
8521 |
0,0221 |
0,028 |
|
*By agreement between the parties, the cables can be manufactured with a return wire of a different cross-section than that shown in the table. |
|||||||
|
XnUHKXS1 8,7/15kV |
|||||||
|
Conductor cross-section |
Return wire cross-section |
Rated thickness of |
Approximate cable outer diameter |
Approximate cable weight |
Max. conductor resistance at temp. |
||
|
insulation |
sheath |
20°C |
90°C |
||||
|
mm2 |
mm2 |
mm |
mm |
kg/km |
Ω/km |
Ω/km |
|
|
50 |
16 |
4,5 |
2,5 |
28,0 |
1057 |
0,387 |
0,495 |
|
70 |
25 |
4,5 |
2,5 |
29,7 |
1363 |
0,268 |
0,343 |
|
95 |
35 |
4,5 |
2,5 |
31,6 |
1703 |
0,193 |
0,247 |
|
120 |
25 |
4,5 |
2,5 |
32,4 |
1857 |
0,153 |
0,196 |
|
120 |
50 |
4,5 |
2,5 |
32,9 |
2082 |
0,153 |
0,196 |
|
150 |
25 |
4,5 |
2,5 |
34,1 |
2160 |
0,124 |
0,159 |
|
150 |
50 |
4,5 |
2,5 |
34,6 |
2385 |
0,124 |
0,159 |
|
185 |
25 |
4,5 |
2,5 |
35,6 |
2514 |
0,0991 |
0,127 |
|
185 |
50 |
4,5 |
2,5 |
36,1 |
2740 |
0,0991 |
0,127 |
|
240 |
25 |
4,5 |
2,5 |
38,0 |
3080 |
0,0754 |
0,097 |
|
240 |
50 |
4,5 |
2,5 |
38,5 |
3300 |
0,0754 |
0,097 |
|
300 |
25 |
4,5 |
2,5 |
40,0 |
3618 |
0,0601 |
0,077 |
|
300 |
50 |
4,5 |
2,5 |
40,5 |
3843 |
0,0601 |
0,077 |
|
400 |
50 |
4,5 |
2,5 |
43,2 |
4821 |
0,0470 |
0,060 |
|
500 |
50 |
4,5 |
2,5 |
46,2 |
5777 |
0,0366 |
0,047 |
|
630 |
50 |
4,5 |
2,6 |
50,7 |
7041 |
0,0283 |
0,036 |
|
800 |
50 |
4,5 |
2,8 |
54,5 |
8687 |
0,0221 |
0,028 |
|
*By agreement between the parties, the cables can be manufactured with a return wire of a different cross-section than that shown in the table. |
|||||||
|
XnUHKXS1 12/20kV |
|||||||
|
Conductor cross-section |
Return wire cross-section |
Rated thickness of |
Approximate cable outer diameter |
Approximate cable weight |
Max. conductor resistance at temp. |
||
|
insulation |
sheath |
20°C |
90°C |
||||
|
mm2 |
mm2 |
mm |
mm |
kg/km |
Ω/km |
Ω/km |
|
|
50 |
16 |
5,5 |
2,5 |
30,1 |
1147 |
0,387 |
0,495 |
|
70 |
25 |
5,5 |
2,5 |
31,5 |
1450 |
0,268 |
0,343 |
|
95 |
35 |
5,5 |
2,5 |
33,6 |
1803 |
0,193 |
0,247 |
|
120 |
25 |
5,5 |
2,5 |
34,4 |
1962 |
0,153 |
0,196 |
|
120 |
50 |
5,5 |
2,5 |
34,9 |
2192 |
0,153 |
0,196 |
|
150 |
25 |
5,5 |
2,5 |
36,1 |
2267 |
0,124 |
0,159 |
|
150 |
50 |
5,5 |
2,5 |
36,6 |
2498 |
0,124 |
0,159 |
|
185 |
25 |
5,5 |
2,5 |
37,6 |
2625 |
0,0991 |
0,127 |
|
185 |
50 |
5,5 |
2,5 |
38,1 |
2855 |
0,0991 |
0,127 |
|
240 |
25 |
5,5 |
2,5 |
40,0 |
3196 |
0,0754 |
0,097 |
|
240 |
50 |
5,5 |
2,5 |
40,5 |
3426 |
0,0754 |
0,097 |
|
300 |
25 |
5,5 |
2,5 |
42,0 |
3740 |
0,0601 |
0,077 |
|
300 |
50 |
5,5 |
2,5 |
42,5 |
3970 |
0,0601 |
0,077 |
|
400 |
50 |
5,5 |
2,5 |
45,2 |
4737 |
0,0470 |
0,060 |
|
500 |
50 |
5,5 |
2,6 |
48,4 |
5940 |
0,0366 |
0,047 |
|
630 |
50 |
5,5 |
2,7 |
53,1 |
7237 |
0,0283 |
0,036 |
|
800 |
50 |
5,5 |
2,8 |
57,1 |
8918 |
0,0221 |
0,028 |
|
*By agreement between the parties, the cables can be manufactured with a return wire of a different cross-section than that shown in the table. |
|||||||
|
XnUHKXS1 18/30kV |
|||||||
|
Conductor cross-section |
Return wire cross-section |
Rated thickness of |
Approximate cable outer diameter |
Approximate cable weight |
Max. conductor resistance at temp. |
||
|
insulation |
sheath |
20°C |
90°C |
||||
|
mm2 |
mm2 |
mm |
mm |
kg/km |
Ω/km |
Ω/km |
|
|
50 |
16 |
8,0 |
2,5 |
35,0 |
1364 |
0,387 |
0,495 |
|
70 |
25 |
8,0 |
2,5 |
36,7 |
1686 |
0,268 |
0,343 |
|
95 |
35 |
8,0 |
2,5 |
38,7 |
1998 |
0,193 |
0,247 |
|
120 |
25 |
8,0 |
2,5 |
39,4 |
2130 |
0,153 |
0,196 |
|
120 |
50 |
8,0 |
2,5 |
39,9 |
2431 |
0,153 |
0,196 |
|
150 |
25 |
8,0 |
2,5 |
41,3 |
2457 |
0,124 |
0,159 |
|
150 |
50 |
8,0 |
2,5 |
41,8 |
2758 |
0,124 |
0,159 |
|
185 |
25 |
8,0 |
2,5 |
42,8 |
2827 |
0,0991 |
0,127 |
|
185 |
50 |
8,0 |
2,5 |
43,3 |
3127 |
0,0991 |
0,127 |
|
240 |
25 |
8,0 |
2,5 |
45,0 |
3407 |
0,0754 |
0,097 |
|
240 |
50 |
8,0 |
2,5 |
45,5 |
3707 |
0,0754 |
0,097 |
|
300 |
25 |
8,0 |
2,5 |
47,4 |
4056 |
0,0601 |
0,077 |
|
300 |
50 |
8,0 |
2,5 |
47,9 |
4180 |
0,0601 |
0,077 |
|
400 |
50 |
8,0 |
2,6 |
50,2 |
5271 |
0,0470 |
0,060 |
|
500 |
50 |
8,0 |
2,7 |
54,1 |
6300 |
0,0366 |
0,047 |
|
630 |
50 |
8,0 |
2,9 |
58,2 |
7596 |
0,0283 |
0,036 |
|
800 |
50 |
8,0 |
3,0 |
61,9 |
9291 |
0,0221 |
0,028 |
|
*By agreement between the parties, the cables can be manufactured with a return wire of a different cross-section than that shown in the table. |
|||||||
Warianty / Variants (51)
| ID | Wariant | Symbol | |
|---|---|---|---|
| 30764 | XnUHKXS 18/30kV 1x800/50 | XnUHKXS1 6/10kV; 8,7/15kV; 12/20kV; 18/30kV |
Wydruk obejmuje opis rodziny i widoczną stronę wariantów. Pełny zestaw można przeglądać kolejnymi stronami.